On , OSHA opened a planned safety inspection of HEAVLIN MANAGEMENT COMPANY, LLC in HAMPTON INN & SUITES-SCOTTSDALE RIVERWALK 9550 E TALKING STICK WAY, SCOTTSDALE, AZ 85256 (NAICS 721110). OSHA activity number 342918570.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HEAVLIN MANAGEMENT COMPANY, LLC
- Site address
- HAMPTON INN & SUITES-SCOTTSDALE RIVERWALK 9550 E TALKING STICK WAY
- City
- SCOTTSDALE
- State
- AZ
- ZIP
- 85256
- Mailing
- 2147 E BASELINE ROAD, TEMPE, AZ 85283
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 18
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 4, 2018
- Abate by
- Apr 16, 2018
- Penalty
- Initial $5,543 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Pantry Storage Room: The 120 volt relocatable power tap designed and listed to provide power to low-powered loads such as computers, printers, radios, etc. was instead used to provide power to two freezers which are considered high-powered loads.
Recent events (2)
- — I (S) $3000
- — Z (S) $5543
1910.305 G01 IV A
- Issued
- Apr 4, 2018
- Abate by
- Apr 16, 2018
- Penalty
- Initial $5,543 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Pantry Storage Area - A flexible cord, approximately 50 feet long, was used as fixed wiring to power a Relocatable Power Tap (RPT). Two individual freezers were plugged in the RPT.
Recent events (2)
- — I (S) $3000
- — Z (S) $5543
More inspections at Heavlin Management Company, LLC
View Heavlin Management Company, LLC's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342918570.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.