On , OSHA opened a complaint safety inspection of CONGLOBAL INDUSTRIES, INC. in 2534 SPRUILL AVE, NORTH CHARLESTON, SC 29405 (NAICS 488390). OSHA activity number 342949930.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Conglobal Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Conglobal Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2534 SPRUILL AVE
City
NORTH CHARLESTON
State
SC
ZIP
29405
Mailing
2534 SPRUILL AVE, NORTH CHARLESTON, SC 29405
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488390
Employees
9
Ownership type
A

4 citations on file for this inspection.

1910.303 F02

Other-than-serious 2 instances 4 exposed
Issued
Apr 12, 2018
Abate by
May 1, 2018
Penalty
Initial $5,543 · Current $5,543
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Northeast corner of the Chassis Shop: Two 120 volt electrical service panels were not marked to show which breakers operated which circuit or piece of equipment.     ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (O) $5543
  • — Z (S) $5543

1910.303 G02 I A

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 12, 2018
Abate by
May 1, 2018
Penalty
Initial $9,239 · Current $7,761 Reduced
29 CFR 1910.303(g)(2)(i)(A): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or by location in a room, vault, or similar enclosure that is accessible only to qualified persons:    a) Northeast Corner of the Chassis Shop: A 240 volt electrical panel had duct tape placed over the live parts in lieu of a proper metal cover.     ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (S) $7761
  • — Z (S) $9239

1910.305 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 12, 2018
Abate by
May 1, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) Northeast corner of the Chassis Shop: The unused openings in the 240 volt electrical panel were covered with duct tape in lieu of a proper metal cover.   ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J02 V

Serious Gravity 5 4 instances 4 exposed
Issued
Apr 12, 2018
Abate by
May 1, 2018
Penalty
Initial $7,391 · Current $0 Reduced
29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered (attachment plug cap not inserted and receptacle covers closed):    a) East side of the Chassis Shop: An outdoor type 120 volt quad box located at the open end of the shed was not equipped with weatherproof covers.     b) Southwest corner of the Chassis Shop: An outdoor type 120 volt quad box located at the open end of the shed was not equipped with weatherproof covers.     c) North side of the Chassis Shop: An outdoor type 120 volt quad box located at the open end of the shed was not equipped with weatherproof covers.     d) Northeast corner of the Chassis Shop: An outdoor type 120 volt duplex box located at the open end of the shed was not equipped with a weatherproof cover.    ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $7391

View Conglobal Industries, INC.'s full OSHA safety record →