SHASTA LAKE, CA —
OSHA Inspection: DEPT. OF THE INTERIOR / BUREAU OF RECLAMATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DEPT. OF THE INTERIOR / BUREAU OF RECLAMATION in 16349 SHASTA DAM BLVD., SHASTA LAKE, CA 96019 (NAICS 924110). OSHA activity number 342996246.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEPT. OF THE INTERIOR / BUREAU OF RECLAMATION
- Site address
- 16349 SHASTA DAM BLVD.
- City
- SHASTA LAKE
- State
- CA
- ZIP
- 96019
- Mailing
- 16349 SHASTA DAM BLVD., SHASTA LAKE, CA 96019
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924110
- Employees
- 170
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.243 C01
- Issued
- Mar 12, 2018
- Abate by
- Apr 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.243(c)(1): Abrasive wheel(s) were used on portable grinder(s) which were not provided with safety guard(s) meeting the requirements specified in 29 CFR 1910.243(c)(1) through (c)(4). In the following locations, four portable abrasive wheel grinders were not provided with safety guards; a) Equipment Garage: one portable abrasive grinder b) Power Plant Building, Welding Shop: three portable abrasive grinders
Recent events (1)
- — Z (S) $0
1910.244 A01 II
- Issued
- Mar 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.244(a)(1)(ii): Rated load(s) of portable jack(s) were not legibly and permanently marked in a prominent location on the jack(s) by casting, stamping, or other suitable means. Equipment Garage: A portable jack stand did not have the rated load capacity marked accordingly. Employees were exposed to crushing hazards.
Recent events (1)
- — Z (S) $0
1910.333 A01
- Issued
- Mar 12, 2018
- Abate by
- Apr 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed were not deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Equipment Garage: Employees were exposed to electrical hazards while working on or near an energized electrical panel inside the garage where flammable vapors were present.
Recent events (1)
- — Z (S) $0
1910.335 A01 I
- Issued
- Mar 12, 2018
- Abate by
- Apr 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not using electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. Equipment Garage: Employees were exposed to electrical hazards while working on or near an energized electrical panel inside the equipment maintenance garage without utilizing face and hand protection equipments.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Mar 12, 2018
- Abate by
- Apr 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit.": Equipment Garage: A designated exit was not marked by a sign reading "Exit".
Recent events (1)
- — Z (O) $0
1910.242 B
- Issued
- Mar 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 P.S.I.: Power Plant, Maintenance Shop: Employees used compressed air at 80 P.S.I. for cleaning work stations and various machines.
Recent events (1)
- — Z (O) $0
More inspections at Dept. of the Interior / Bureau of Reclamation
View Dept. of the Interior / Bureau of Reclamation's full OSHA safety record →
More inspections in this industry (NAICS 924110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342996246.