Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BECC ELECTRIC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of BECC ELECTRIC in 10 DUNHAM AVENUE, CELORON, NY 14720 (NAICS 238210). OSHA activity number 342996931.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Becc Electric — free Get an email when a new federal OSHA severe-injury report for Becc Electric is published. One employer, no account, unsubscribe in one click.
Establishment
BECC ELECTRIC
Site address
10 DUNHAM AVENUE
City
CELORON
State
NY
ZIP
14720
Mailing
1007 CENTRAL AVENUE, DUNKIRK, NY 14048
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
A

1 citation on file for this inspection.

1926.403 B02

Serious Gravity 1 2 instances 12 exposed
Issued
Mar 9, 2018
Penalty
Initial $3,880 · Current $2,910 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) On or about 2/28/18 at a construction project for a new hotel located at 10 Dunham Avenue, Celoron, New York; on the 2nd floor, a 4"x4" receptacle box with pre-punched knockouts was connected to non-metallic sheathed cable to provide temporary power for the project. The receptacles were being used to provide power to portable tools and were not mounted as required in the listing an labeling requirements for the boxes.    NO ABATEMENT CERTIFICATION REQUIRED    b) On or about 2/28/18 at a construction project for a new hotel located at 10 Dunham Avenue, Celoron, New York; portable electric heaters were wired using non-metallic sheathed cable. The non-metallic sheathed cable was run on the floor in work areas and not attached, fastened or protected in accordance with the listing and labeling requirements.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2910
  • — Z (S) $3880

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342996931.