NEW HARTFORD, NY —
OSHA Inspection: AXIOM CONSTRUCTION, LLC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AXIOM CONSTRUCTION, LLC. in AT HOME, 4645 COMMERCIAL DRIVE, NEW HARTFORD, NY 13413 (NAICS 236220). OSHA activity number 343012621.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AXIOM CONSTRUCTION, LLC.
- Site address
- AT HOME, 4645 COMMERCIAL DRIVE
- City
- NEW HARTFORD
- State
- NY
- ZIP
- 13413
- Mailing
- 129 WUNSCHE LOOP, SPRING, TX 77373
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 40
- Ownership type
- A
Citations
7 citations on file for this inspection.
1926.25 A
- Issued
- Apr 12, 2018
- Penalty
- Initial $3,880 · Current $3,880
General-duty citation text
29 CFR 1926.25(a): During the course of construction, alteration, or repairs, debris was not kept cleared from work areas, passageways, and in and around buildings or other structures: a) South end of building, on or about 2-27-18: Employees were working in a building where demolition debris was stored on the floor with nails and screws protruding from boards.
Recent events (1)
- — Z (S) $3880
1926.350 A09
- Issued
- Apr 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.350(a)(9): Compressed gas cylinders were not secured in an upright position at all times: a) North end of building, center, on or about 2-27-18: Employees were working in an area immediately adjacent to a compressed gas cylinder that was not secured.
Recent events (1)
- — Z (S) $0
1926.403 B02
- Issued
- Apr 12, 2018
- Penalty
- Initial $3,880 · Current $3,880
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) South wall of building, on or about 2-27-18: Employees were using two 4"x4" galvanized receptacle boxes that were not being used as "listed and labeled", in that they were not used as designed or for their intended purpose.
Recent events (1)
- — Z (S) $3880
1926.405 G02 III
- Issued
- Apr 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used only in continuous lengths without splice or tap and/or hard service flexible cords No. 12 or larger with repairs were not repaired as required so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced: a) East wall of building, southeast corner, on or about 2-27-18: Employees were operating various hand held power tools and working around a branch circuit that was not continuous in length, in that the splice was not in a box.
Recent events (1)
- — Z (S) $0
1926.403 I02
- Issued
- Apr 12, 2018
- Penalty
- Initial $5,174 · Current $5,174
General-duty citation text
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures: a) West wall of building, on or about 2-27-18: Employees were working in the immediate vicinity of an energized 12 capacity circuit breaker panel that was missing 5 circuit breakers, exposing the employees to energized parts inside the panel. a) Northeast corner of building, on or about 2-27-18: Employees were working in the immediate vicinity of an energized circuit breaker panel that was missing its cover, exposing the employees to energized parts inside the panel.
Recent events (1)
- — Z (S) $5174
1926.404 B01 II
- Issued
- Apr 12, 2018
- Penalty
- Initial $3,880 · Current $3,880
General-duty citation text
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection: a) South wall of building, on or about 2-27-18: Employees were operating various hand held power tools that were powered through receptacles that were not protected by a ground fault circuit interrupter (GFCI). b) East wall of building, southeast corner, on or about 2-27-18: Employees were operating various hand held power tools that were powered through receptacles that did not have a continuous path to ground due to improper internal wiring, rendering the GFCI protection inoperable.
Recent events (1)
- — Z (S) $3880
1926.404 F06
- Issued
- Apr 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: a) East wall of building, southeast corner, on or about 2-27-18: Employees were operating various hand held power tools that were powered through receptacles that did not have a continuous path to ground due to improper internal wiring.
Recent events (1)
- — Z (S) $0
More inspections at Axiom Construction, LLC.
View Axiom Construction, LLC.'s full OSHA safety record →
More inspections in this industry (NAICS 236220)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343012621.