Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PANKO ELECTRICAL & MAINTENANCE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PANKO ELECTRICAL & MAINTENANCE, INC. in AT HOME, 4645 COMMERCIAL DRIVE, NEW HARTFORD, NY 13413 (NAICS 238210). OSHA activity number 343012654.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Panko Electrical & Maintenance, INC. — free Get an email when a new federal OSHA severe-injury report for Panko Electrical & Maintenance, INC. is published. One employer, no account, unsubscribe in one click.
Site address
AT HOME, 4645 COMMERCIAL DRIVE
City
NEW HARTFORD
State
NY
ZIP
13413
Mailing
1080 CHENANGO STREET, BINGHAMTON, NY 13901
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
40
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Deleted Serious Gravity 1 2 instances 3 exposed
Issued
Apr 10, 2018
Penalty
Initial $3,880 · Current $0 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) South wall of building, on or about 2-27-18:  Employees were using two 4"x4" galvanized receptacle boxes that were not being used as "listed and labeled", in that they were not used as designed or for their intended purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3880

1926.405 G02 III

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Apr 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(2)(iii):  Flexible cords were not used only in continuous lengths without splice or tap and/or hard service flexible cords No. 12 or larger with repairs were not repaired as required so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced:     a) East wall of building, southeast corner, on or about 2-27-18:  Employees were  operating various hand held power tools and working around a branch circuit that was not continuous in length, in that the splice was not in a box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.403 I02

Deleted Serious Gravity 5 2 instances 3 exposed
Issued
Apr 10, 2018
Penalty
Initial $6,467 · Current $0 Reduced
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures:     a) West wall of building, on or about 2-27-18:  Employees were working in the immediate vicinity of an energized 12 capacity circuit breaker panel that was missing 5 circuit breakers, exposing the employees to energized parts inside the panel.     a) Northeast corner of building, on or about 2-27-18:  Employees were working in the immediate vicinity of an energized circuit breaker panel that was missing its cover, exposing the employees to energized parts inside the panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6467

1926.404 B01 II

Deleted Serious Gravity 10 3 instances 3 exposed
Issued
Apr 10, 2018
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:    a) South wall of building, on or about 2-27-18:  Employees were operating various hand held power tools that were powered through receptacles that were not protected by a ground fault circuit interrupter (GFCI).     b) East wall of building, southeast corner, on or about 2-27-18:  Employees were operating various hand held power tools that were powered through receptacles that did not have a continuous path to ground due to improper internal wiring, rendering the GFCI protection inoperable.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9054

1926.404 F06

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Apr 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:    a) East wall of building, southeast corner, on or about 2-27-18:  Employees were operating various hand held power tools that were powered through receptacles that did not have a continuous path to ground due to improper internal wiring.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Panko Electrical & Maintenance, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343012654.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.