OSHA Inspection: ARMY MARYSVILLE ARMED FORCES RESERVE CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ARMY MARYSVILLE ARMED FORCES RESERVE CENTER in 13613 40TH AVE, NE, MARYSVILLE, WA 98271 (NAICS 928110). OSHA activity number 343014510.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army Marysville Armed Forces Reserve Center — free Get an email when a new federal OSHA severe-injury report for Army Marysville Armed Forces Reserve Center is published. One employer, no account, unsubscribe in one click.
Site address
13613 40TH AVE, NE
City
MARYSVILLE
State
WA
ZIP
98271
Mailing
13613 40TH AVE, NE, MARYSVILLE, WA 98271
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
25
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 7 instances 25 exposed
Issued
Apr 17, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:  a)  At the Facility, where electrical equipment not used as listed included:  1. Second Floor G3 Area, where a relocatable power tap was used to supply power to appliances including the Mr. Coffee 12 cup drip coffee maker.   2. Cubicle 8, where a relocatable power tap was used to supply power to appliances including the Hamilton Beach refrigerator and a small aquarium.   3. Room 261-C, where a relocatable power tap was used to supply power to appliances including the portable floor heater and a fan. (Item Corrected)  4. Room 285-A, where a relocatable power tap was used to supply power to appliances including the Sanyo refrigerator and the Oster microwave oven.  5. Room 283-B, where a relocatable power tap was used to supply power to appliances including the West Bend microwave oven and the Candle warmer.  6. Room 283-A, where a relocatable power tap was used to supply power to appliances including the Oster water kettle.  7. Room 242-E, where a relocatable power tap was daisy chained with an orange extension cord and used to supply power to appliances including the Simply Perfect microwave oven.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Other-than-serious 4 instances 25 exposed
Issued
Apr 17, 2018
Abate by
Sep 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3):  The employer did not assure that portable fire extinguishers were subjected to an annual maintenance check:   a) Facility, where employees would evacuate the building in the event of a fire, annual inspections were not conducted for fire extinguishers including, but not limited to:  1. G-3 Area, where the Amerex fire extinguisher was equipped with an inspection tag dated January 2016.   2. Suite 260 hallway, where the Amerex fire extinguisher was equipped with an inspection tag dated January 2016.   3. G-8 Area, where the Amerex fire extinguisher was equipped with an inspection tag dated January 2016.   4. G-1 Cubicle Area, where the Amerex fire extinguisher was equipped with an inspection tag dated January 2016.
Recent events (1)
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 25 exposed
Issued
Apr 17, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:   a) Room 283-B, where the power cord for the relocatable power tap was pulled from the strain relief exposing insulated conductors.
Recent events (1)
  • — Z (O) $0