Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCI WEST - MCB CAMP PENDLETON FACILITIES MAINTENANCE DIVISION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of MCI WEST - MCB CAMP PENDLETON FACILITIES MAINTENANCE DIVISION in CLB-5 AREA 21 CAMP DEL MAR, CAMP PENDLETON, CA 92055 (NAICS 561210). OSHA activity number 343034294.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MCI West - MCB Camp Pendleton Facilities Maintenance Division — free Get an email when a new federal OSHA severe-injury report for MCI West - MCB Camp Pendleton Facilities Maintenance Division is published. One employer, no account, unsubscribe in one click.
Site address
CLB-5 AREA 21 CAMP DEL MAR
City
CAMP PENDLETON
State
CA
ZIP
92055
Mailing
PO BOX 555055 ATTN: MARIO FERREIRA - BASE SAFETY CENTER, CAMP PENDLETON, CA 92055
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
206
Ownership type
D

6 citations on file for this inspection.

1910.30 A01

Serious Gravity 10 1 instance 7 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.30(a)(1): The employer did not provide training for each employee exposed to fall hazards and who used personal fall protection systems or is required to be trained as specified elsewhere in this subpart prior to May 17, 2017:  Camp Del Mar CLB-5 Compound: Effective training on fall hazards and the proper use of personal fall arrest systems was not provided to employees working at heights. Employees work in aerial lift trucks performing maintenance tasks, such as repairing lighting systems. Employees were exposed to fall hazards.
Recent events (1)
  • — Z (S) $0

1910.67 C02 V

Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.67(c)(2)(v): A personal fall arrest or travel restraint system that meets the requirements in subpart I of this part was not worn and attached to the boom or basket when working from an aerial lift:  Camp Del Mar CLB-5 Compound: On March 19, 2018, an employee was performing maintenance on the overhead lighting from the bucket of an Altec aerial truck without the leg straps of his personal fall arrest system secured. The employee was exposed to fall hazards.
Recent events (1)
  • — Z (S) $0

1910.333 A

Serious Gravity 10 1 instance 7 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:  Facilities Maintenance Division / Camp Del Mar: Electrical safety-related work practices were not developed and implemented to protect employees during high voltage electrical work. On March 19, 2018, employee(s) were performing maintenance on and/or near electrical equipment without de-energizing. Employees were exposed to electrical shock hazards at 480 volts.
Recent events (1)
  • — Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not de-energized before the employee worked on or near them:  Camp Del Mar, CLB-5 Compound: On March 19, 2018, employee(s) were performing maintenance on and/or near the overhead lights without it de-energized. Employees were exposed to electrical shock hazards at 480 volts.
Recent events (1)
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  Camp Del Mar, CLB-5 Compound: On March 19, 2018, employee(s) were performing maintenance on and/or near energized 480 volt overhead lights without hand protection. Employees were exposed to electrical shock hazards.
Recent events (1)
  • — Z (S) $0

1910.132 D01

Repeat Gravity 10 1 instance 7 exposed
Issued
May 15, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):  Facilities Maintenance Division / Camp Del Mar: An assessment was not conducted to determine the hazards associated with electrical-related work and the associated personal protective equipment that would be required for the task. Employees were exposed to electrical shock hazards.  MCI West - MCB Camp Pendleton Facilities Maintenance Division was previously cited for a violation of this occupational safety and health standard or its equivalent standard [29 CFR 1910.132(d)(1)], which was contained in OSHA inspection number 1288750, citation number 1, item number 1 and was affirmed as a final order on April 25, 2018, with respect to a workplace located at Building 2296, MCB Camp Pendleton, California 92055.
Recent events (1)
  • — Z (R) $0

View MCI West - MCB Camp Pendleton Facilities Maintenance Division's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343034294.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.