Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COMMERCIAL MILLWORK SPECIALIST, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of COMMERCIAL MILLWORK SPECIALIST, INC. in 1518B 28TH ST., GULFPORT, MS 39501 (NAICS 238350). OSHA activity number 343052528.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Commercial Millwork Specialist, INC. — free Get an email when a new federal OSHA severe-injury report for Commercial Millwork Specialist, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1518B 28TH ST.
City
GULFPORT
State
MS
ZIP
39501
Mailing
1518B 28TH ST., GULFPORT, MS 39501
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238350
Employees
27
Ownership type
A

13 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 5 instances 27 exposed
Issued
May 22, 2018
Abate by
May 31, 2018
Penalty
Initial $6,467 · Current $3,880 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  (a) Site wide - On or about March 29, 2018 employees performing routine maintenance on a planer machine,  dual saw, Router  machine and other equipment but the employer did not develop lockout/tagout written procedures to control potentially stored hazardous energy.
Recent events (2)
  • — I (S) $3880.2
  • — Z (S) $6467

1910.178 L

Serious Gravity 1 1 instance 27 exposed
Issued
May 22, 2018
Abate by
Jun 7, 2018
Penalty
Initial $3,880 · Current $2,328 Reduced
29 CFR 1910.178(l): Operators were not trained in the safe operation of powered industrial trucks:   (a) Throughout the facility - On or about March 29, 2018 employees were operating the forklifts without being trained on the safe operation of the forklifts.
Recent events (2)
  • — I (S) $2328
  • — Z (S) $3880

1910.213 D01

Serious Gravity 5 1 instance 2 exposed
Issued
May 22, 2018
Abate by
May 31, 2018
Penalty
Initial $6,467 · Current $3,880 Reduced
29 CFR 1910.213(d)(1): Circular handfed crosscut table saw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut:  (a) Solid wood working building - On or about March 29, 2018 employees operating the Powermatic table saw with the blade guard missing.
Recent events (2)
  • — I (S) $3880.2
  • — Z (S) $6467

1910.215 A04

Serious Gravity 1 1 instance 2 exposed
Issued
May 22, 2018
Abate by
May 31, 2018
Penalty
Initial $3,880 · Current $2,328 Reduced
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work.  (a) Solid Wood Working Building #2 - On or about March 29, 2018 employees were using the DeWalt bench grinder that had the right work rest missing and the left work rest adjusted to 3/4 inch from the wheel.
Recent events (2)
  • — I (S) $2328
  • — Z (S) $3880

1910.305 B01 II

Serious Gravity 5 2 instances 27 exposed
Issued
May 22, 2018
Abate by
May 24, 2018
Penalty
Initial $6,467 · Current $3,880 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  (a) West wall in Office building #1 - On or about March 29, 2018 employees must use the panel boxes located on the wall to disconnect the main power to the equipment with multiple breakers missing inside the panels.
Recent events (2)
  • — I (S) $3880.2
  • — Z (S) $6467

1910.305 G01 IV A

Serious Gravity 1 4 instances 27 exposed
Issued
May 22, 2018
Abate by
May 24, 2018
Penalty
Initial $3,880 · Current $2,328 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a) Throughout building #1 - On or about March 29, 2018 employer was using extension cords as permanent wiring for wood working equipment.
Recent events (2)
  • — I (S) $2328
  • — Z (S) $3880

1910.147 C07

Other-than-serious 6 instances 27 exposed
Issued
May 22, 2018
Abate by
Jun 7, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7): The employer shall provide training to ensure that the purpose and functions of the energy control program are understood by employees and that the knowledge and skills required for the safe application, useage, and removal of the energy controls are acquired by employees.    (a) Site wide - On or about March 29, 2018 employees performing  maintenance and blade replacement on the planner, table saw, dual saw , router and other equipment  have not received any training on lock out tag out.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E03

Other-than-serious 7 instances 27 exposed
Issued
May 22, 2018
Abate by
May 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  (a) Through out the facility - On or about March 29, 2018 employer failed to perform annual maintenance check on the portable fire extinguishers.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.242 B

Other-than-serious 3 instances 27 exposed
Issued
May 22, 2018
Abate by
May 24, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:  (a) Throughout the facility - On or about March 29, 2018 employees were using compressed air that was set at 92 psi, not the required 30 psi to clean saw dust off of themselves.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 2 instances 27 exposed
Issued
May 22, 2018
Abate by
May 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  (a) Office building #1 west wall - On or about March 29, 2018 there are two electrical panels that have multiple circuits feeding power throughout the building that are not clearly labeled to indicate its purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01

Other-than-serious 1 instance 27 exposed
Issued
May 22, 2018
Abate by
May 24, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a) Solid wood working building #2 - On or about March 29, 2018 electrical panel box on east wall is blocked with wood working material preventing access to the panel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV B

Other-than-serious 2 instances 27 exposed
Issued
May 22, 2018
Abate by
May 25, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  (a) Building #2 & 3 - On or about March 29, 2018 employer had 2 extension cords to supply power to wood working equipment and lights that was running through the wall to the outlet on the other side.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G02 II

Other-than-serious 1 instance 27 exposed
Issued
May 22, 2018
Abate by
May 25, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:  (a) Office building #1 - On or before March 29, 2018 electrical cable cord for Dyna Pack scissor lift table has 2 splices in the cord that was repaired using wire nuts and electricians tape lying on the floor.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Commercial Millwork Specialist, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343052528.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.