EUGENE, OR —
OSHA Inspection: DEPARTMENT OF VETERANS AFFAIRS, CBOC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEPARTMENT OF VETERANS AFFAIRS, CBOC in 3355 CHAD DR, EUGENE, OR 97408 (NAICS 621111). OSHA activity number 343082780.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEPARTMENT OF VETERANS AFFAIRS, CBOC
- Site address
- 3355 CHAD DR
- City
- EUGENE
- State
- OR
- ZIP
- 97408
- Mailing
- 3355 CHAD DR, EUGENE, OR 97408
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 621111
- Employees
- 300
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.36 G02
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. Coffee Bar Storage and Office area- (a) Materials, supplies, and equipment, limited the access from 18" to 24", delaying the egress from the space and exposing employees to serious injuries in the event of a fire.
Recent events (1)
- — Z (S) $0
1910.159 C10
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: Coffee Bar Storage and Office area- (a) Coffee cups are stacked and within 5 inches of the automatic sprinkler heads for the fire suppression system, exposing employees to serious injuries in the event of a fire.
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: Coffee Bar- (a) The unidentified portable fire extinguisher was hidden by the equipment and was not mounted, potentially exposing employees to injuries while accessing the equipmentduring a fire event.
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Coffee Bar- (a) The portable fire extinguisher was not being inspected monthly and was past due on the annual maintenance checks.
Recent events (1)
- — Z (S) $0
1910.157 G01
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage firefighting. Coffee Bar- (a) Employee(s) indicated they would use the available fire extinguisher to extinguish incipient fires, but were unfamiliar with proper techniques and limitations of portable fire extinguisher.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Aug 20, 2018
- Abate by
- Sep 14, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: or in the alternative NFPA 70 of the NEC, Article 210, Part II. Branch-Circuit Ratings 210.21(B)(2): Total Cord-and-Plug-Connected Load. Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle shall not supply a total cord-and-plug-connected load in excess of the maximum specified in Table 210.21(B)(2).Max load amperes for 20 amperes receptacle is 16 amperes. Pearl Pod Area- (a) Employee(s) were exposed to a fire hazard created by numerous devices connected to a 20 ampere branch circuit, which exceeded the maximum total cord-and-plug-connected load rating.
Recent events (1)
- — Z (O) $0
More inspections at Department of Veterans Affairs, Cboc
View Department of Veterans Affairs, Cboc's full OSHA safety record →
More inspections in this industry (NAICS 621111)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343082780.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.