ARLINGTON, VA —
OSHA Inspection: EMCOR GOVERNMENT SERVICES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of EMCOR GOVERNMENT SERVICES, INC. in 100 WASHINGTON BLVD, ARLINGTON, VA 22202 (NAICS 811310). OSHA activity number 343099867.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EMCOR GOVERNMENT SERVICES, INC.
- Site address
- 100 WASHINGTON BLVD
- City
- ARLINGTON
- State
- VA
- ZIP
- 22202
- Mailing
- 2800 CRYSTAL DR., SUITE 600, ARLINGTON, VA 22202
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 100
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 II B
- Issued
- May 22, 2018
- Abate by
- Jun 18, 2018
- Penalty
- Initial $12,934 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedures did not clearly and specifically outline the steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy. a) EMCOR Government Services, Pentagon: On or about 04/05/2018, the energy control procedure did not specifically specify how and what to use to block the kinetic energy generated by the exhaust fan, as a result an employee right ring finger tip was amputated. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records
Recent events (3)
- — F (O) $3500
- — C (S) $12934
- — Z (S) $12934
1910.147 C05 I
- Issued
- May 22, 2018
- Abate by
- Jun 18, 2018
- Penalty
- Initial $12,934 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing or blocking of machines or equipment from energy sources: a) EMCOR Government Services, Pentagon: On or about 04/05/2018, the employer failed to provide the proper hardware to block the exhaust fan from rotating as a result an employee's right ring finger tip was caught between the belt and pulley. The pulley rotated after the rag used to secure the energy dislodged. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
- — F (O) $3500
- — C (S) $12934
- — Z (S) $12934
1910.147 C06 II
- Issued
- May 22, 2018
- Abate by
- Jun 18, 2018
- Penalty
- Initial $12,934 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed: a) EMCOR Government Services, Pentagon: On or about April 05, 2018, the employer did not certify that a periodic inspection was conducted for exhaust fans that contained multiple energy sources including kinetic energy. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
- — F (O) $3500
- — C (S) $12934
- — Z (S) $12934
1904.32 A04
- Issued
- May 22, 2018
- Penalty
- Initial $1,848 · Current $0 Reduced
General-duty citation text
29 CFR 1904.32(a)(4): The employer did not post an OSHA 300A Form or equivalent by February 1 thru April 30. a) EMCOR Government Services, Pentagon: On or about April 05, 2018, the employer failed to post the annual summary of work-related injuries and illnesses pertaining to the establishment. No abatement certification or documentation required.
Recent events (3)
- — F (O) $0
- — C (O) $1848
- — Z (O) $1848
1904.39 A02
- Issued
- May 22, 2018
- Penalty
- Initial $9,239 · Current $0 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report an in-patient hospitalization, amputation, or loss of an eye as a result of a work-related incident to OSHA within twenty-four (24) hours: a) EMCOR Government Services, Pentagon: On or about 04/05/2018, the employer failed to report an amputation within 24 hours after an employee's right ring finger tip was caught between the V-belt and pulley of an exhaust fan. No abatement certification or documentation required.
Recent events (3)
- — F (O) $0
- — C (O) $9239
- — Z (O) $9239
More inspections at Emcor Government Services, INC.
View Emcor Government Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 811310)
More inspections in VA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343099867.