OSHA Inspection: NATIONAL PARK SERVICE, OLYMPIC NATIONAL PARK, U.S. GEOLOGICAL SURVEY BUILDING

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of NATIONAL PARK SERVICE, OLYMPIC NATIONAL PARK, U.S. GEOLOGICAL SURVEY BUILDING in 600 EAST PARK AVENUE, U.S. GEOLOGIC SURVEY BUILDING, PORT ANGELES, WA 98362 (NAICS 713990). OSHA activity number 343134029.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service, Olympic National Park, U.S. Geological Survey Building — free Get an email when a new federal OSHA severe-injury report for National Park Service, Olympic National Park, U.S. Geological Survey Building is published. One employer, no account, unsubscribe in one click.
Site address
600 EAST PARK AVENUE, U.S. GEOLOGIC SURVEY BUILDING
City
PORT ANGELES
State
WA
ZIP
98362
Mailing
600 EAST PARK AVENUE, PORT ANGELES, WA 98362
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713990
Employees
2
Ownership type
D

6 citations on file for this inspection.

1910.305 B02 I

Serious Gravity 1 1 instance 1 exposed
Issued
May 16, 2018
Abate by
May 29, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a)  Wildlife Biologist Office;  The light switch did not have a cover and insulated wires were visible.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 1 exposed
Issued
May 16, 2018
Abate by
Jun 20, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)  Garage;  The GE deep freezer was powered by a black extension cord.    b)  Garage;  The Frigidaire deep freezer was powered by an orange extension cord.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Other-than-serious 1 instance 2 exposed
Issued
May 16, 2018
Abate by
May 31, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a)   The exit discharge door (which leads directly outside) did not have an exit sign.
Recent events (1)
  • — Z (O) $0

1910.37 B05

Other-than-serious 1 instance 2 exposed
Issued
May 16, 2018
Abate by
Jun 5, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  a)  The door which leads to the garage did not have a NOT AN EXIT or STORAGE/GARAGE sign
Recent events (1)
  • — Z (O) $0

1910.157 E02

Other-than-serious 4 instances 2 exposed
Issued
May 16, 2018
Abate by
Jun 20, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a)     Kitchen;  The First Alert fire extinguisher had its last monthly inspection in August, 2013.   b)     Kitchen;  The Buckeye fire extinguisher had its last monthly inspection in August 2013.   c)     Hallway;  The Buckeye fire extinguisher had its last monthly inspection in August, 2013.  d)     Garage;  The Buckeye fire extinguisher had its last monthly inspection in August, 2013.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 4 instances 2 exposed
Issued
May 16, 2018
Abate by
Jun 20, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  a)  Kitchen;  The First Alert fire extinguisher had its last annual inspection in December, 2011.   b)  Kitchen;  The Buckeye fire extinguisher had its last monthly inspection in December, 2011.  c)  Hallway;  The Buckeye fire extinguisher had its last monthly inspection in December, 2011.  d)  Garage;  The Buckeye fire extinguisher had its last monthly inspection in December, 2011.   Note:  Applies to any extinguishers provided in the workplace.  Maintenance check includes an internal examination, except extinguishers with stored pressure.
Recent events (1)
  • — Z (O) $0