TUCKER, GA ·
OSHA Inspection: BROS SIGN SERVICES, LLC
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of BROS SIGN SERVICES, LLC in 3936 LAVISTA ROAD, TUCKER, GA 30084 (NAICS 561790). OSHA activity number 343155487.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BROS SIGN SERVICES, LLC
- Site address
- 3936 LAVISTA ROAD
- City
- TUCKER
- State
- GA
- ZIP
- 30084
- Mailing
- 3708 ATLANTA HIGHWAY SUITE B, ATHENS, GA 30606
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561790
- Employees
- 5
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.332 B01
- Issued
- Nov 2, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $3,880 · Current $3,880
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: On or about May 3, 2018 at 3936 LaVista Road, Tucker, Georgia, the employer did not ensure that employees performing electrical repairs received training in the safety-related work practices such as but not limited to verification that electrical defects and/or hazards were eliminated after repairs were made. An employee was exposed to live electrical parts after opening the signs frame to install light bulbs.
Recent events (2)
- · I (S) $3880
- · Z (S) $3880
1910.332 B01
- Issued
- Nov 2, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments. On or about May 11 at 3936 LaVista Road, Tucker, Georgia, the employer failed to train the employees on the use of safety related work practices such as, working on or near live parts, de-energizing and testing equipment and LOTO requirements after equipment is de-energized.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.333 B02
- Issued
- Nov 2, 2018
- Abate by
- Dec 21, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were de-energized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): On or about May 3, 2018 at 3936 Lavista Road, Tucker, Georgia, the employees making repairs to the sign turned off the circuit, but did not lock and tag out the circuit.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.333 B02 IV B
- Issued
- Nov 2, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized: On or about May 3, 2018 at 3936 LaVista Road, Tucker, Georgia after replacing the ballast and prior to replacing lamps in the sign, a qualified person did not use testing equipment to verify that the wall mounted disconnect actually deenergized the sign.
Recent events (2)