Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SOUTHWESTERN ELECTRIC POWER COMPANY- TURK POWER PLANT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOUTHWESTERN ELECTRIC POWER COMPANY- TURK POWER PLANT in 3711 HIGHWAY 355 SOUTH, FULTON, AR 71838 (NAICS 221112). OSHA activity number 343164745.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Southwestern Electric Power Company- Turk Power Plant — free Get an email when a new federal OSHA severe-injury report for Southwestern Electric Power Company- Turk Power Plant is published. One employer, no account, unsubscribe in one click.
Site address
3711 HIGHWAY 355 SOUTH
City
FULTON
State
AR
ZIP
71838
Mailing
428 TRAVIS STREET, SHREVEPORT, LA 71101
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
118
Ownership type
A

3 citations on file for this inspection.

1910.147 C04 II B

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Oct 3, 2018
Abate by
Oct 19, 2018
Penalty
Initial $9,239 · Current $0 Reduced
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedure did not clearly and specifically specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:  On May 8, 2018, and times prior thereto, at the Rotary Car Unloader Building Supply Blower, the employer had not developed specific energy isolation control procedures and training for employees required to service and/or perform maintenance on the Aerovent Backward Inclined Utility Blower (BUIB), Model #33 BUIB, Serial #J-3953296-2-1.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9239

1910.147 C04 II D

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Oct 3, 2018
Abate by
Oct 19, 2018
Penalty
Initial $9,239 · Current $0 Reduced
29 CFR 1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control:   On or about May 8, 2018, and times prior thereto, at the Rotary Car Unloader Building Supply Fan, where the employer did not ensure employees isolated the stored energy to the Aerovent Backward Inclined Utility Blower (BUIB), Model #33 BUIB, Serial #J-3953296-2-1 prior to verifying tension of the dual v-belts on the motor drive powering the blower.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9239

1910.145 C02 I

Other-than-serious 1 instance 15 exposed
Issued
Oct 3, 2018
Abate by
Oct 19, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.145(c)(2)(i): Caution signs were not used to warn against potential hazards or to caution against unsafe practices:   On May 8, 2018, and times prior thereto, at the Rotary Car Unloader Building Supply Blower, the employer did not ensure caution sign(s) were installed to alert employees against placing any part of their body near the pinch point areas of the belts and pulleys of the Aerovent Backward Inclined Utility Blower (BUIB), Model #33 BUIB, Serial #J-3953296-2-1 during service and maintenance activities.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343164745.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.