YOUNGWOOD, PA —
OSHA Inspection: FIRESTONE BUILDING PRODUCTS, LLC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FIRESTONE BUILDING PRODUCTS, LLC. in 102 AVENUE A, YOUNGWOOD, PA 15697 (NAICS 326150). OSHA activity number 343164935.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FIRESTONE BUILDING PRODUCTS, LLC.
- Site address
- 102 AVENUE A
- City
- YOUNGWOOD
- State
- PA
- ZIP
- 15697
- Mailing
- 102 AVENUE A, YOUNGWOOD, PA 15697
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326150
- Employees
- 35
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 D03 I D
- Issued
- Sep 18, 2018
- Penalty
- Initial $4,712 · Current $12,000
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): The employer did not maintain an accurate listing of the location, function, and inspection information for all Relief Valves (RV) within a covered process. a) Facility, 102 Avenue A, Youngwood PA, on or about May 17, 2018 - The Company failed to maintain accurate information for all pressure relief valves to the Pentane Storage Tank.
Recent events (2)
- — I (S) $12000
- — Z (S) $4712
1910.119 E03 I
- Issued
- Sep 18, 2018
- Abate by
- Nov 5, 2018
- Penalty
- Initial $5,543 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process: a) Facility, 102 Avenue A, Youngwood PA, on or about May 17, 2018 - The Process Hazard Analysis (PHA) did not consider/identify the hazards related to the loss of nitrogen for blanketing the Pentane Storage Tank.
Recent events (2)
- — I (O) $0
- — Z (S) $5543
1910.119 F01 III B
- Issued
- Sep 18, 2018
- Abate by
- Nov 5, 2018
- Penalty
- Initial $5,543 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(B): The employer's Standard Operating Procedures did not include precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment; a) Facility, 102 Avenue A, Youngwood, PA, on or about May 17, 2018 - The Company failed to identify in the Standard Operating Procedures for offloading Pentane the need for fire resistant clothing (FRC).
Recent events (2)
- — I (O) $0
- — Z (S) $5543
1910.119 N
- Issued
- Sep 18, 2018
- Penalty
- Initial $4,712 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(n): The employer's emergency action plan did not include procedures for handling small releases: a) Facility, 102 Avenue A, Youngwood PA, on or about May 17, 2018 - The employer did not include a procedure in its emergency action plan that instructs employees how to distinguish between small releases/spills and large releases/spills and what employee actions are required in both instances.
Recent events (2)
- — I (O) $0
- — Z (S) $4712
More inspections at Firestone Building Products, LLC.
View Firestone Building Products, LLC.'s full OSHA safety record →
More inspections in this industry (NAICS 326150)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343164935.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.