OSHA Inspection: RELIANCE AEROPRODUCTS INTERNATIONAL, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RELIANCE AEROPRODUCTS INTERNATIONAL, INC in 950 6TH AVE., MANSFIELD, TX 76063 (NAICS 326291). OSHA activity number 343166831.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Reliance Aeroproducts International, INC — free Get an email when a new federal OSHA severe-injury report for Reliance Aeroproducts International, INC is published. One employer, no account, unsubscribe in one click.
Site address
950 6TH AVE.
City
MANSFIELD
State
TX
ZIP
76063
Mailing
950 6TH AVE., MANSFIELD, TX 76063
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326291
Employees
15
Ownership type
A

6 citations on file for this inspection.

1910.219 D01

Serious Gravity 5 1 instance 3 exposed
Issued
May 22, 2018
Abate by
Jun 20, 2018
Penalty
Initial $3,696 · Current $1,800 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o).        At a facility located at 950 6th Ave., Mansfield, Texas: in the autoclave room, the employer did not ensure the vacuum pump pulleys were guarded exposing employees to being caught-in/in-going nip points of rotating pulleys.
Recent events (2)
  • — I (S) $1800
  • — Z (S) $3696

1910.219 E03 I

Serious Gravity 5 1 instance 3 exposed
Issued
May 22, 2018
Abate by
Jun 20, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o).     At a facility located at 950 6th Ave., Mansfield, Texas: in the autoclave room, the employer did not ensure the vacuum pump belt was guarded exposing employees to being caught-in/in-going nip points of rotating belt.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01

Serious Gravity 1 1 instance 3 exposed
Issued
May 22, 2018
Abate by
Jun 20, 2018
Penalty
Initial $1,995 · Current $900 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:       At a facility located at 950 6th Ave., Mansfield, Texas: in the fuel cell repair shop, the employer did not replace damaged electrical wall outlets exposing employees to shock hazards.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1995

1910.303 E

Serious Gravity 1 1 instance 3 exposed
Issued
May 22, 2018
Penalty
Initial $1,885 · Current $900 Reduced
29 CFR 1910.303(e): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary.        At a facility located at 950 6th Ave., Mansfield, Texas: in the shop areas, the employer had electrical panel boxes that energized machinery which were not marked with voltage ratings:      a)     220 breaker box in the fuel cell repair shop.    b)     240 volt panel in the manufacturing room.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1885

1910.305 G02 III

Other-than-serious 1 instance 3 exposed
Issued
May 22, 2018
Abate by
Jun 20, 2018
Penalty
Initial $373 · Current $100 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.         At a facility located at 950 6th Ave., Mansfield, Texas: in the fuel cell repair shop, the employer did not ensure strain relief device was provided to prevent tension on the repair shop work table power cord used to energize portable tools exposing employees to shock hazards.
Recent events (2)
  • — I (O) $100
  • — Z (O) $373

1910.334 A02 I

Other-than-serious 1 instance 3 exposed
Issued
May 22, 2018
Abate by
Jun 20, 2018
Penalty
Initial $373 · Current $100 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):       At a facility located at 950 6th Ave., Mansfield, Texas: in the fuel cell repair shop, the employer used an extension cord with a missing ground pin to energize small portable tools exposing employees to electrical shock hazards.
Recent events (2)
  • — I (O) $100
  • — Z (O) $373

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343166831.