Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LIGHTPATH TECHNOLOGIES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of LIGHTPATH TECHNOLOGIES, INC. in 50 S BUCKHOUT ST # 106, IRVINGTON, NY 10533 (NAICS 446130). OSHA activity number 343176574.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lightpath Technologies, INC. — free Get an email when a new federal OSHA severe-injury report for Lightpath Technologies, INC. is published. One employer, no account, unsubscribe in one click.
Site address
50 S BUCKHOUT ST # 106
City
IRVINGTON
State
NY
ZIP
10533
Mailing
50 S BUCKHOUT ST # 106, IRVINGTON, NY 10533
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
446130
Employees
50
Ownership type
A

4 citations on file for this inspection.

1910.147 C01

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2018
Penalty
Initial $9,054 · Current $6,800 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:      (a) The employer did not develop, document and utilized an energy control procedure (lockout/tag out program) to ensure that all required elements of the procedure were understood by employees and that the knowledge and skills required for the safe application, usage and removal of the energy controls were acquired by employees performing repair work on a machine or equipment, such as; but not limited, to the vacuum chamber "A" high voltage supply control unit
Recent events (2)
  • — I (S) $6800
  • — Z (S) $9054

1910.147 C04 I

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2018
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:    location: Optical lens coating lab; vacuum chamber "A",    on or about: 4/24/18    a) The employer did not have adequate procedures developed, documented and utilized for work including but not limited to troubleshooting, vacuum chamber "A", control unit power triode cooling lines while energized; exposing employees to electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9054

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2018
Penalty
Initial $9,054 · Current $6,800 Reduced
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed were not deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs:    location: Optical lens coating lab; vacuum chamber "A",    on or about: 4/24/18    a) Adequate maintenance procedures were not developed, documented and utilized for work including but not limited to troubleshooting and addressing the power triode leaking cooling lines while the high voltage supply control unit was energized exposing employees to electrical shock hazard.
Recent events (2)
  • — I (S) $6800
  • — Z (S) $9054

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2018
Penalty
Initial $9,054 · Current $6,800 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed    Location:  Optical lens coating lab; vacuum chamber "A" high voltage control unit.    On or about: 4/24/2018    (a) An employee was working near energized components, power triode and triode transformer, to visually inspect and address leaking cooling lines was not provided and did not use insulated gloves, flame retardant clothing, insulated boots, insulated hard hat and insulated face shield to protect the head, feet, body, arms and hands from the hazards of electrocution and arc flash hazards.
Recent events (2)
  • — I (S) $6800
  • — Z (S) $9054

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343176574.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.