DEXTER, MO —
OSHA Inspection: STODDARD COUNTY SHELTERED WORKSHOP
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of STODDARD COUNTY SHELTERED WORKSHOP in 1118 CENTER ST., DEXTER, MO 63841 (NAICS 562920). OSHA activity number 343205803.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STODDARD COUNTY SHELTERED WORKSHOP
- Site address
- 1118 CENTER ST.
- City
- DEXTER
- State
- MO
- ZIP
- 63841
- Mailing
- P.O. BOX 505, DEXTER, MO 63841
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562920
- Employees
- 48
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B02
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $3,880 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: In the recycling sorting work area, a fourplex outlet was connected to a vertical piece of conduit that was not secured; the conduit could be readily moved from side to side. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $2000
- — Z (S) $3880
1910.303 B07 IV
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a. In Recycling Area 1, a light switch was used that was not supported (the connection was loose). b. In Recycling Area 1, sections of electrical conduit were separated. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: The main electrical panel had circuit breaker openings that were not closed. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: In recycling area 1, there was no strain relief for the cable at the bottom of #7 disconnect. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $3,880 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: In recycling area 2, a cooling fan was used without a ground pin, resulting in a possible electrical shock. Abatement documentation is required for this violation.
Recent events (2)
- — I (S) $2000
- — Z (S) $3880
1910.22 A02
- Issued
- Jun 19, 2018
- Abate by
- Jul 23, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(2): The floor of each workroom was not maintained in a clean and, to the extent feasible, in a dry condition: In the warehouse a leaking roof resulted in water on the floor where supervisors walked and operated forklifts. Abatement documentation is required for this violation.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Stoddard County Sheltered Workshop
View Stoddard County Sheltered Workshop's full OSHA safety record →
More inspections in this industry (NAICS 562920)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343205803.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.