Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: NEWLAND CONSTRUCTION INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NEWLAND CONSTRUCTION INC. in 821 45TH STREET, BROOKLYN, NY 11219 (NAICS 236220). OSHA activity number 343206934.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Newland Construction INC. for free Get an email when a new federal OSHA severe-injury report for Newland Construction INC. is published. One employer, no account, unsubscribe in one click.
Site address
821 45TH STREET
City
BROOKLYN
State
NY
ZIP
11219
Mailing
1654 78TH STREET, BROOKLYN, NY 11214
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
15
Ownership type
Private (A)

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 3 instances 1 exposed
Issued
Dec 3, 2018
Penalty
Initial $2,956 · Current $1,900 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification.    Location: 821 45th Street, Brooklyn, NY; Basement    a) A 4 inch junction box housing a light switch in an energized system was not mounted.  It was used to power the ceiling light fixture in the room.    b) A 4 inch junction box housing a receptacle in an energized system was not mounted.  It was used to power an extension cord.    c) A 4 inch junction box housing a receptacle was connected to a flexible cord and was not mounted.  It was placed loosely on the floor and being used to energize a battery charger.
Recent events (2)
  • · I (S) $1900
  • · Z (S) $2956

1926.405 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 3, 2018
Penalty
Initial $2,956 · Current $1,900 Reduced
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers.  In an energized installation, each outlet box did not have a cover, faceplate, or fixture canopy.    Location: 821 45th Street, Brooklyn, NY; Basement        a) A 4 inch junction box also being used as housing of a light switch was not installed with a cover.  The switch was energized and powering the ceiling light fixture.    b) A 4 inch junction box being used as housing of a receptacle was not installed with a cover.  The receptacle was being used to power an extension cord.    c) A 4 inch junction box housing a receptacle connected to a flexible cord was being used as an extension cord.  The  receptacle was not provided with a faceplate.  It was being used to power a battery charger.
Recent events (2)
  • · I (S) $1900
  • · Z (S) $2956

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343206934.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.