Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HOLOD'S HOME AND GARDEN CENTER

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HOLOD'S HOME AND GARDEN CENTER in 700-706 RIDGE PIKE, LAFAYETTE HILL, PA 19444 (NAICS 444130). OSHA activity number 343249033.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Holod'S Home and Garden Center — free Get an email when a new federal OSHA severe-injury report for Holod'S Home and Garden Center is published. One employer, no account, unsubscribe in one click.
Site address
700-706 RIDGE PIKE
City
LAFAYETTE HILL
State
PA
ZIP
19444
Mailing
700-706 RIDGE PIKE, LAFAYETTE HILL, PA 19444
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
444130
Employees
9
Ownership type
A

2 citations on file for this inspection.

1910.305 G01 IV A

Serious Gravity 1 1 instance 10 exposed
Issued
Aug 6, 2018
Abate by
Aug 14, 2018
Penalty
Initial $1,663 · Current $1,663
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)  Greenhouse - On or about June 20, 2018, an extension cord energized to 120 volts AC was being used to power installed overhead lighting.
Recent events (1)
  • — Z (S) $1663

1910.305 G01 IV D

Serious Gravity 1 1 instance 10 exposed
Issued
Aug 6, 2018
Abate by
Aug 14, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:  a)  Greenhouse - On or about June 20, 2018, an extension cord energized to 120 volts AC was attached to the ceiling members and wall columns while providing power to a lighting fixture.