Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: KILGORE SAW COMPANY

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of KILGORE SAW COMPANY in 6723 LUMSDEN RD., NORTH LITTLE ROCK, AR 72118 (NAICS 332216). OSHA activity number 343256483.

Watch Kilgore SAW Company — free Get an email when a new federal OSHA severe-injury report for Kilgore SAW Company is published. One employer, no account, unsubscribe in one click.
Establishment
KILGORE SAW COMPANY
Site address
6723 LUMSDEN RD.
City
NORTH LITTLE ROCK
State
AR
ZIP
72118
Mailing
6723 LUMSDEN RD., NORTH LITTLE ROCK, AR 72118
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332216
Employees
7
Ownership type
A

8 citations on file for this inspection.

1910.141 A03 I

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1663.00 · Current $0.00 Reduced
29 CFR 1910.141(a)(3)(i): Places of employment were not kept clean to the extent that the nature of the work allowed:  On or about June 27, 2018 and times prior thereto, the ceiling tiles above the Simonds welder in the corner had visible signs of water damage, was broken in multiple areas, and caving in above where employees operating the welders stood. This condition exposed employees to struck-by hazards from falling debris.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1663

1910.147 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2772.00 · Current $1500.00 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    On or about June 27, 2018 and times prior thereto, the employer had not developed an energy control program with machine specific isolation procedures and periodic inspections for employees required to, but not limited to, perform maintenance on the ALO, and the welders. This condition exposed employees to shock and caught in hazards in the event of an unexpected start-up.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2772

1910.147 C04 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:(a)  On or about June 27, 2018 and times prior thereto, the employer had not developed a written procedures for employees required to, but not limited to, perform maintenance on the ALO, and the welders. This condition exposed employees to shock and caught in hazards in the event of an unexpected start-up.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A03 II

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2772.00 · Current $1500.00 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):(a)     On or about June 27, 2018 and times prior thereto, the guard on the ALO blade shear was not adequate to keep employees' hands out of the point of operation during the operating cycles. This condition exposed employees to amputation hazards.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2772

1910.303 G01

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $2772.00 · Current $1500.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    On or about June 27, 2018 and times prior thereto, the knife switch disconnects for the following equipment were partially blocked and not readily accessible in the following instances:    a) The large Simonds welder located on the side wall.   b) The middle Simonds welder, or Jeremy's welder, located in the middle of the three welders along the side wall.    Employees used the welders to weld the ends of band-saw blades together. This condition exposed employees to shock hazards in the event of an emergency.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2772

1910.305 G01 III

Deleted Serious Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $1663.00 · Current $0.00 Reduced
29 CFR 1910.305(g)(1)(iii): Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph:(a)  On or about June 27 and times prior thereto, extension cords were being used as permanent wiring in the following instances:   a) Providing power to the over-head lights by the Simonds welders. b) Providing power to the fans mounted on the ceiling.  This condition exposes employees to shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1663

1910.134 C02 I

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $311.00 · Current $0.00 Reduced
29 CFR 1910.134(c)(2)(i): Respirator users were not provided with the information contained in Appendix D to 29 CFR 1910.134 when the employer determined that any voluntary respirator use was permissible:    On or about June 27, 2018 and times prior thereto, the employer provided employees with Moldex 2200N95 Series particulate respirators for voluntary use but did not provide employees with the information found in Appendix D. This condition exposed employees to respiratory hazards due to misuse.
Recent events (2)
  • — I (O) $0
  • — Z (O) $311

1910.303 E01 II

Other-than-serious 3 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(e)(1)(ii):  Electrical equipment were not marked giving voltage, current, wattage or other ratings as necessary:  On or about June 27, 2018 and times prior thereto, , panel boxes were observed without voltage markings in the following instances:  Instance a: Panel boxes supplying power to the 3 Simonds welders used to join the ends of the cut band-saws along the side wall, and Instance b: Panel box supplying power to ALO cutter, labeled HIGH LEG B.  This condition exposed employees to shock hazards in the event of an emergency.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343256483.