OSHA Inspection: LETTERKENNY ARMY DEPOT

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of LETTERKENNY ARMY DEPOT in ATTN: SAFETY DEPARMENT 1 OVERCASH AVENUE BUILDING 14, CHAMBERSBURG, PA 17201 (NAICS 921190). OSHA activity number 343315180.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Letterkenny Army Depot — free Get an email when a new federal OSHA severe-injury report for Letterkenny Army Depot is published. One employer, no account, unsubscribe in one click.
Site address
ATTN: SAFETY DEPARMENT 1 OVERCASH AVENUE BUILDING 14
City
CHAMBERSBURG
State
PA
ZIP
17201
Mailing
ATTN: SAFETY DEPARTMENT 1 OVERCASH AVENUE BUILDING 14, CHAMBERSBURG, PA 17201
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
921190
Employees
900
Ownership type
D

6 citations on file for this inspection.

1910.106 E02 II B 2

Serious Gravity 5 1 instance 350 exposed
Issued
Jan 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons:  (a)  NORTH EXTERIOR OF PAINT KITCHEN, BUILDING 350 - The employer staged for use three (3) 55 gallon drums of Tan 686A paint (category 2 flammable liquid) and two (2) 55 gallon drums of Epoxy Hardener Part B (category 3 flammable liquid) near the exterior of the North Side of the paint kitchen.  Also staged in the near vicinity were two (2) 55 gallon drums of MIL-T--81772b T1 Polyurethane Reducer (category 2 flammable liquid) and three 55 gallon drums of liquid paint waste (category 2 flammable liquid).  The total quantity of combined category 2 and category 3 flammable liquids not properly stored totaled 550 gallons, on or about July 19, 2018.  No abatement certification or documentation required.
Recent events (1)
  • — Z (S) $0

1910.106 E02 IV A

Serious Gravity 10 2 instances 23 exposed
Issued
Jan 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(iv)(a): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were not kept in covered containers when not actually in use:    (a)  BUILDING 350, PAINT KITCHEN - Employees performed paint kitchen operations in the paint kitchen structure, and the small steel thinner pot that was used to supply the polyurethane reducer (category 2 flammable liquid) for flushing the paint pump that was used to pump Tan paint into the pressurized paint pot was not kept covered when not in use, on or about July 19, 2018.  (b)  BUILDING 350, PAINT SPRAY BOOTHS - Employees performed painting operations in the paint spray booths.  Employees routinely filled pot liners with polyurethane reducer from a 55 gallon drum and placed the liner in the spray booth without a cover where it would remain under the spray cart until ready to be used for flushing the spray guns, on or about July 19, 2018.  No abatement certification or documentation required.
Recent events (1)
  • — Z (S) $0

1910.106 E06 I

Serious Gravity 10 1 instance 7 exposed
Issued
Jan 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors:  (a)  BUILDING 350, PAINT KITCHEN - The employer did not ensure that employees utilized non-sparking tools to remove and install bungs and also the syphon connection in the tops of the 55 gallon drums of paint and paint related materials used in the paint kitchen, on or about July 19, 2018.  No abatement certification or documentation required.
Recent events (1)
  • — Z (S) $0

1910.106 E06 II

Serious Gravity 10 2 instances 7 exposed
Issued
Jan 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container are electrically interconnected:  (a)  BUILDING 350, PAINT KITCHEN - Employees used Sherwin Williams R91K00020 MIL-T-81772B T1 Polyurethane Reducer (Category 2 flammable liquid, flashpoint 37.4F, boiling point 172.4F) to flush and clean the pump after refilling the Tan paint tank, and the dispensing tube from the pump was not bonded to the small thinner pot that the reducer was circulated through and stored in, on or about July 19, 2018.  (b)  BUILDING 350, PAINT KITCHEN - Employees transferred Sherwin Williams R91K00020 MIL-T-81772B T1 Polyurethane Reducer (Category 2 flammable liquid, flashpoint 37.4F, boiling point 172.4F) to the small thinner pot using a diaphragm pump, and he dispensing tube from the pump was not bonded to the small thinner pot that the reducer was being transferred to, on or about July 19, 2018.  No abatement certification or documentation required.
Recent events (1)
  • — Z (S) $0

1960.59 A

Serious Gravity 10 1 instance 7 exposed
Issued
Jan 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1960.59(a): The Agency did not provide specialized job safety and health training appropriate to the work performed by the employee:  (a)  PAINT KITCHEN, BUILDING 350 - The employer did not ensure that employees received appropriate training to operate the paint kitchen located in building 350, on or about July 19, 2018.  (b)  PAINT KITCHEN, BUILDING 350 - The employer did not ensure that employees were trained to correctly ground and bond paint kitchen equipment, including but not limited to diaphragm pumps, 55 gallon drums of paint and paint related materials, and pressurized paint pots, on or about July 19, 2018.  (c)  PAINT KITCHEN, BUILDING 350 - The employer did not ensure that employees were trained to transport 55 gallon drums of flammable liquids and load the drums into the paint kitchen area located in building 350. A forklift equipped with a clamp device was sometimes used to place full drums of product onto the wheeled drum cradles and at other times, employees transported drums using wooden pallets, followed by manual force to move the drums into position, on or about July 19, 2018.  No abatement certification or documentation required.
Recent events (1)
  • — Z (S) $0

1960.29 D

Deleted Other-than-serious 1 instance 3 exposed
Issued
Jan 15, 2019
Abate by
Feb 19, 2019
Penalty
Initial $0 · Current $0
29 CFR 1960.29(d): The Agency did not make the investigative reports available to the Secretary or his authorized representative when it was requested:  (a)  LETTERKENNY ARMY DEPOT - The results of the AMCOM formal accident investigation that was conducted as result of the fire and explosion incident that occurred at the Letterkenny Army Depot facility in the building 350 paint kitchen on July 19, 2018 was not provided to the Harrisburg Area OSHA office when they were requested, on or about November 19, 2018.  (b)  LETTERKENNY ARMY DEPOT - The results of the AR-15-6 investigation that was conducted by AMCOM as result of the fire and explosion incident that occurred at the Letterkenny Army Depot facility in the building 350 paint kitchen on July 19, 2018 was not provided to the Harrisburg Area OSHA office when it was requested, on or about November 19, 2018.  No abatement certification or documentation required.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

View Letterkenny Army Depot's full OSHA safety record →