OSHA Inspection: BIMBO BAKERIES USA INC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of BIMBO BAKERIES USA INC in 5005 SW WENGER DR, TOPEKA, KS 66609 (NAICS 311812). OSHA activity number 343334264.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bimbo Bakeries USA INC — free Get an email when a new federal OSHA severe-injury report for Bimbo Bakeries USA INC is published. One employer, no account, unsubscribe in one click.
Site address
5005 SW WENGER DR
City
TOPEKA
State
KS
ZIP
66609
Mailing
5005 SW WENGER DR, TOPEKA, KS 66609
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311812
Employees
78
Ownership type
A

2 citations on file for this inspection.

1910.263 I07 I

Other-than-serious 1 instance 8 exposed
Issued
Dec 26, 2018
Abate by
Jan 23, 2019
Penalty
Initial $6,097 · Current $3,353 Reduced
29 CFR 1910.263(i)(7)(i): Undersides of conveyors were not completely enclosed where they passed over a main aisleway, regularly occupied work area, or passageway to prevent broken chains or other material from falling:    Employees working near the dough transfer conveyor for breadline DD-2 were exposed to struck by hazards from the overhead conveyor that was not enclosed.
Recent events (2)
  • — I (O) $3353.35
  • — Z (S) $6097

1910.305 G01 IV A

Other-than-serious 1 instance 2 exposed
Issued
Dec 26, 2018
Penalty
Initial $5,183 · Current $2,851 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Employees were exposed to electrical shock and fire hazards.  Employees were exposed to electrical hazards associated using temporary flexible cords in lieu of permanent wiring.  In the maintenance room the Air Master fan mounted on column F-13 above the Jet Mill uses a temporary flexible cord to power the fan.
Recent events (2)
  • — I (O) $2850.65
  • — Z (S) $5183

View Bimbo Bakeries USA INC's full OSHA safety record →