BROOKLYN, NY —
OSHA Inspection: WJP BUILDERS CORP.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WJP BUILDERS CORP. in 1214 40TH ST., BROOKLYN, NY 11218 (NAICS 236118). OSHA activity number 343346987.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WJP BUILDERS CORP.
- Site address
- 1214 40TH ST.
- City
- BROOKLYN
- State
- NY
- ZIP
- 11218
- Mailing
- 5314 16TH AVENUE SUITE 295, BROOKLYN, NY 11204
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236118
- Employees
- 3
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.405 A02 II A
- Issued
- Dec 21, 2018
- Penalty
- Initial $3,880 · Current $3,880
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(A): Temporary wiring conductors did not run as multi-conductor cord or cable assemblies or within raceways, and are subjected to physical damage. a) Basement, near building entrance: Employees were excavating in the basement and were using a light bulb in temporary wiring for general illumination. The light bulb was connected to wires from a circuit breaker panel that did not run as a cord or cable, and were exposed to physical damage. On or about 07/27/18.
Recent events (2)
- — I (S) $3880
- — Z (S) $3880
1926.405 A02 II E
- Issued
- Dec 21, 2018
- Penalty
- Initial $2,772 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage. a) Basement: Employees were excavating in the basement and were using a light bulb in temporary wiring for general illumination. The light bulb was not protected from accidental contact or breakage. On or about 07/27/18.
Recent events (2)
- — I (S) $0
- — Z (S) $2772
1926.405 B02
- Issued
- Dec 21, 2018
- Penalty
- Initial $3,880 · Current $2,000 Reduced
General-duty citation text
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers. a) Basement, near building entrance: Two energized electrical panel boards were not provided with covers. Employees were excavating in the basement and were using the panel boards to control electrical power on site. On or about 07/27/18.
Recent events (2)
- — I (S) $2000
- — Z (S) $3880
1926.405 G02 III
- Issued
- Dec 21, 2018
- Penalty
- Initial $2,772 · Current $1,120 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap. a) Basement: Employees were excavating in the basement and were using a light bulb in temporary wiring for general illumination. The light bulb was installed on an electric light socket with a flexible cord, which was spliced to an extension cord. On or about 07/27/18.
Recent events (2)
- — I (S) $1120
- — Z (S) $2772
More inspections at WJP Builders Corp.
View WJP Builders Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 236118)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343346987.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.