OSHA Inspection: BUCKEYE NISSAN, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BUCKEYE NISSAN, INC. in 3959 PARKWAY LANE, HILLIARD, OH 43026 (NAICS 811121). OSHA activity number 343392205.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Buckeye Nissan, INC. — free Get an email when a new federal OSHA severe-injury report for Buckeye Nissan, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3959 PARKWAY LANE
City
HILLIARD
State
OH
ZIP
43026
Mailing
3820 PARKWAY LANE, HILLIARD, OH 43026
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811121
Employees
100
Ownership type
A

2 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 5 instances 12 exposed
Issued
Sep 25, 2018
Abate by
Oct 5, 2018
Penalty
Initial $4,947 · Current $3,463 Reduced
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.   a. On or about August 16, 2018, in the electrical room, each circuit breaker in the north service panel-A was not marked to indicate its purpose, thereby exposing employees to an electrical and/or fire hazard.    b. On or about August 16, 2018, in the electrical room, each circuit breaker in the south service panel-A was not marked to indicate its purpose, thereby exposing employees to an electrical and/or fire hazard.   c. On or about August 16, 2018, in the electrical room, the north disconnect was not marked to indicate its purpose, thereby exposing employees to an electrical and/or fire hazard.   d. On or about August 16, 2018, in the electrical room, the disconnect for the compressor on the main switch cabinet was not legibly marked to indicate its purpose, thereby exposing employees to an electrical and/or fire hazard.   e. On or about August 16, 2018, in the electrical room, the disconnect for the transformer feeds panel A and west wall on the main switch cabinet was misidentified as to its purpose, thereby exposing employees to an electrical and/or fire hazard.
Recent events (2)
  • — I (S) $3462.9
  • — Z (S) $4947

1910.305 B01 II

Serious Gravity 5 2 instances 12 exposed
Issued
Sep 25, 2018
Abate by
Oct 5, 2018
Penalty
Initial $4,947 · Current $3,463 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.   a. On or about August 16, 2018, in the electrical room, the north service panel-A had four openings in the right side due to knockouts that were missing and/or conduit that was removed, thereby exposing employees to an electrical hazard.   b. On or about August 16, 2018, in the electrical room, the north unidentified disconnect had an opening on the top side due to a knockout that was missing, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $3462.9
  • — Z (S) $4947