Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCGEE INDUSTRIES, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of MCGEE INDUSTRIES, INC. in 9 CROZERVILLE RD, ASTON, PA 19014 (NAICS 325998). OSHA activity number 343397295.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mcgee Industries, INC. — free Get an email when a new federal OSHA severe-injury report for Mcgee Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
9 CROZERVILLE RD
City
ASTON
State
PA
ZIP
19014
Mailing
PO BOX 2425, ASTON, PA 19014
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325998
Employees
15
Ownership type
A

6 citations on file for this inspection.

1910.106 E03 IV A

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $3,789 · Current $3,789
29 CFR 1910.106(e)(3)(iv)(a): Emergency drainage systems were not provided to direct flammable liquid leakage and fire protection water to a safe location. This may require curbs, scuppers, or special drainage systems to control the spread of fire; see paragraph (b)(2)(vii)(b) of this section.  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to fire hazards due the potential for ignited flammable liquids to spread outside the solvent mixing room in the event of a fire.  An emergency drainage system and/or other means capable of containing and directing the spread of a fire protection water to a safe location in the facility was not available.  This condition was observed on or about August 16, 2018.
Recent events (1)
  • — Z (S) $3789

1910.134 C02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $3,789 · Current $3,789
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use does not present a health hazard to the user:  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to health hazards associated with improper use and maintenance of air purifying respirators such as but not limited to pulmonary and cardiac distress.  Employees voluntarily wore Sperian 2000 series half mask air purifying respirators and 3M 7500 half mask air purifying respirators without the employer establishing and implementing the elements of a written respiratory protection program.  This condition was documented to occur on or about and at times prior to August 16, 2018 in the warehouse.
Recent events (1)
  • — Z (S) $3789

1910.134 E01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to health hazards associated with improper use of air purifying respirators such as but not limited to pulmonary and cardiac distress.  Employees voluntarily wore Sperian 2000 series half mask air purifying respirators and 3M 7500 half mask air purifying respirators without the employer providing medical evaluations.  This condition was documented to occur on or about and at times prior to August 16, 2018 in the warehouse.
Recent events (1)
  • — Z (S) $0

1910.134 F01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT):  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to health hazards associated with improper use of air purifying respirators such as but not limited to pulmonary and cardiac distress.  Employees voluntarily wore Sperian 2000 series half mask air purifying respirators and 3M 7500 half mask air purifying respirators without the employer ensuring the employees could pass an appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT).  This condition was documented to occur on or about and at times prior to August 16, 2018 in the warehouse.
Recent events (1)
  • — Z (S) $0

1910.307 C02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $3,789 · Current $3,789
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location:  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to fire hazards due to the potential for ignition of flammable vapors inside the solvent mixing room.  The emergency exit sign and light fixture installed inside the solvent mixing room is not of the approved for type for Class 1 Division 2 locations.  This condition was observed on or about August 16, 2018.
Recent events (1)
  • — Z (S) $3789

1910.307 D

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 7, 2019
Abate by
Feb 27, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.307(d): Conduits in hazardous (classified) locations were not threaded:  a) Jobsite: 9 Crozerville Rd, Aston, PA 19014 - Employees are exposed to fire hazards due to the potential for ignition of flammable vapors inside the solvent mixing room.  Metal clad cable was used instead of threaded conduit to feed the emergency exit sign and light fixture.  This condition was observed on or about August 16, 2018.
Recent events (1)
  • — Z (S) $0

View Mcgee Industries, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343397295.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.