Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WESCOM, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WESCOM, INC. in GOBLLER 6-35-26TFH WELL SITE, NEW TOWN, ND 58763 (NAICS 238210). OSHA activity number 343418430.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Wescom, INC. — free Get an email when a new federal OSHA severe-injury report for Wescom, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
WESCOM, INC.
Site address
GOBLLER 6-35-26TFH WELL SITE
City
NEW TOWN
State
ND
ZIP
58763
Mailing
3959 EAST CALVARY ROAD, DULUTH, MN 55803
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
80
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 11, 2019
Abate by
Jan 24, 2019
Penalty
Initial $9,054 · Current $5,000 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    (a) On or about August 17, 2018 for employees exposed to electrical hazards where MC jacketed cable was not properly installed into a Crouse-Hinds TMC4140 fitting at the Gobbler 6-35-26TFH well site near New Town, North Dakota.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $9054

1926.405 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jan 11, 2019
Abate by
Jan 24, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor and so connected to all boxes, fittings, and cabinets as to provide effective electrical continuity:  (a) On or about August 17, 2018 for employees exposed to electrical hazards where Type MC jacketed cable was not properly installed into a Crouse-Hinds TMC4140 cable fitting at a service disconnect panel at the Gobbler 6-35-26TFH well site near New Town, North Dakota.