COLUMBUS, OH —
OSHA Inspection: FRONTIER ELECTRIC, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of FRONTIER ELECTRIC, INC. in 3680 EASTON MARKET, COLUMBUS, OH 43219 (NAICS 238210). OSHA activity number 343422168.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FRONTIER ELECTRIC, INC.
- Site address
- 3680 EASTON MARKET
- City
- COLUMBUS
- State
- OH
- ZIP
- 43219
- Mailing
- 5755 WESTBOURNE AVENUE, COLUMBUS, OH 43213
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 20
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.21 B02
- Issued
- Sep 27, 2018
- Abate by
- Oct 17, 2018
- Penalty
- Initial $3,696 · Current $2,587 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury. a. On or about August 23, 2018, and at times thereto, employees performed electrical work on energized electrical equipment. The employer did not effectively train employees on electrical safe work practices to ensure safety from electrical shock and arc flash hazards.
Recent events (2)
- — I (S) $2587.2
- — Z (S) $3696
1926.403 A
- Issued
- Sep 27, 2018
- Penalty
- Initial $3,696 · Current $2,587 Reduced
General-duty citation text
29 CFR 1926.403(a): Approval. All electrical conductors and equipment shall be approved. a. Located onsite at 3680 Easton Market in Columbus, Ohio: On or about August 27, 2018, a 120 volt romex cord connection was used as a flexible cord to temporary supply electric to the building outlets and lighting circuits from a portable generator. The unapproved connection and splice wrapped with electrical tape exposed employees to an electrical shock and fire hazard.
Recent events (2)
- — I (S) $2587.2
- — Z (S) $3696
1926.95 A
- Issued
- Sep 27, 2018
- Abate by
- Oct 17, 2018
- Penalty
- Initial $5,174 · Current $3,622 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, shall be provided, used, and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact. a. Located onsite at 3680 Easton Market in Columbus, Ohio: On or about August 23, 2018, employees were removing the load wires from an energized 480 volt meter socket. The employer did not provide personal protective equipment to protect employees from electrical shock and arc flash hazards.
Recent events (2)
- — I (S) $3621.8
- — Z (S) $5174
1926.416 A01
- Issued
- Sep 27, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(a)(1): No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means. a. Located onsite at 3680 Easton Market in Columbus, Ohio: On or about August 23, 2018, two employees were removing the load wires from an energized 480 volt meter socket. The employer did not ensure that employees performing the work were protected from electric shock and arc flash hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Frontier Electric, INC.
View Frontier Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343422168.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.