OSHA Inspection: FCC POLLOCK/FEDERAL CORRECTIONAL INSTITUTION (FCI)

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of FCC POLLOCK/FEDERAL CORRECTIONAL INSTITUTION (FCI) in 1000 AIRBASE ROAD, POLLOCK, LA 71467 (NAICS 922140). OSHA activity number 343433348.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch FCC Pollock/Federal Correctional Institution (FCI) — free Get an email when a new federal OSHA severe-injury report for FCC Pollock/Federal Correctional Institution (FCI) is published. One employer, no account, unsubscribe in one click.
Site address
1000 AIRBASE ROAD
City
POLLOCK
State
LA
ZIP
71467
Mailing
P. O. BOX 1000, POLLOCK, LA 71467
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
850
Ownership type
D

1 citation on file for this inspection.

1910.303 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Feb 14, 2019
Abate by
Mar 6, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about 01/17/2019, at the CUP Cooling Tower, the employer did not ensure that the Square D Heavy Duty Safety Switch (600V/100A) that housed the Cooling Tower Fan #3 disconnect was installed properly per its listing/labeling for outdoor use (NEMA Type 3R), which left several unused holes/openings on the back of the enclosure.  Therefore, the enclosure did not provide adequate protection against the intrusion of water and other foreign matter.