OSHA Inspection: UNI-TEMP REFRIGERATION, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of UNI-TEMP REFRIGERATION, INC. in 2200 LITHONIA INDUSTRIAL BLVD., LITHONIA, GA 30058 (NAICS 238220). OSHA activity number 343462420.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Uni-Temp Refrigeration, INC. — free Get an email when a new federal OSHA severe-injury report for Uni-Temp Refrigeration, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2200 LITHONIA INDUSTRIAL BLVD.
City
LITHONIA
State
GA
ZIP
30058
Mailing
4487 S. OLD PEACHTREE RD. #2, NORCROSS, GA 30071
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
5
Ownership type
A

2 citations on file for this inspection.

1910.119 D03 II

Serious Gravity 1 1 instance 50 exposed
Issued
Nov 8, 2018
Penalty
Initial $3,880 · Current $2,328 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.  On 8/8/18, at the Lithonia facility, the employer did not ensure Ammonia engine room doors were tight-fitting, self closing, opened outward from the room and were equipped with panic hardware. There were 3 doors that were not of this type.
Recent events (2)
  • — I (S) $2328
  • — Z (S) $3880

1910.119 H03 IV

Serious Gravity 10 1 instance 5 exposed
Issued
Nov 8, 2018
Abate by
Dec 28, 2018
Penalty
Initial $9,054 · Current $5,432 Reduced
29 CFR 1910.119(h)(3)(iv): The contract employer did not assure that each contract employee follows the safety rules of the facility including the safe work practices required by paragraph (f)(4) of this section.  On 8/8/2018, at the job site of 2200 Lithonia Industrial Blvd., Lithonia, Georgia, employees were exposed to Ammonia exposure hazards as the employer did not develop and implement required safe work practices. Instances included:  a - The employer did not develop specific written Lockout/Tagout procedures for employees replacing a valve on a 2 in. HP liquid line on an active Ammonia refrigeration system July 4th, 2018 and for compressor service/maintenance in June, 2018.  b - The employer did not require or document Hot Work permits when employees performed welding operations to an active ammonia system July 4th, 2018.
Recent events (2)
  • — I (S) $5432.4
  • — Z (S) $9054

View Uni-Temp Refrigeration, INC.'s full OSHA safety record →