LITHONIA, GA —
OSHA Inspection: UNI-TEMP REFRIGERATION, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of UNI-TEMP REFRIGERATION, INC. in 2200 LITHONIA INDUSTRIAL BLVD., LITHONIA, GA 30058 (NAICS 238220). OSHA activity number 343462420.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNI-TEMP REFRIGERATION, INC.
- Site address
- 2200 LITHONIA INDUSTRIAL BLVD.
- City
- LITHONIA
- State
- GA
- ZIP
- 30058
- Mailing
- 4487 S. OLD PEACHTREE RD. #2, NORCROSS, GA 30071
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 5
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 D03 II
- Issued
- Nov 8, 2018
- Penalty
- Initial $3,880 · Current $2,328 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On 8/8/18, at the Lithonia facility, the employer did not ensure Ammonia engine room doors were tight-fitting, self closing, opened outward from the room and were equipped with panic hardware. There were 3 doors that were not of this type.
Recent events (2)
- — I (S) $2328
- — Z (S) $3880
1910.119 H03 IV
- Issued
- Nov 8, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $9,054 · Current $5,432 Reduced
General-duty citation text
29 CFR 1910.119(h)(3)(iv): The contract employer did not assure that each contract employee follows the safety rules of the facility including the safe work practices required by paragraph (f)(4) of this section. On 8/8/2018, at the job site of 2200 Lithonia Industrial Blvd., Lithonia, Georgia, employees were exposed to Ammonia exposure hazards as the employer did not develop and implement required safe work practices. Instances included: a - The employer did not develop specific written Lockout/Tagout procedures for employees replacing a valve on a 2 in. HP liquid line on an active Ammonia refrigeration system July 4th, 2018 and for compressor service/maintenance in June, 2018. b - The employer did not require or document Hot Work permits when employees performed welding operations to an active ammonia system July 4th, 2018.
Recent events (2)
- — I (S) $5432.4
- — Z (S) $9054
More inspections at Uni-Temp Refrigeration, INC.
View Uni-Temp Refrigeration, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238220)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343462420.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.