OSHA Inspection: SAMSON TUG AND BARGE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SAMSON TUG AND BARGE, INC. in 8046 REZANOF DRIVE KODIAK TERMINAL, KODIAK, AK 99615 (NAICS 488320). OSHA activity number 343475950.

Watch Samson TUG AND Barge, INC. — free Get an email when a new federal OSHA severe-injury report for Samson TUG AND Barge, INC. is published. One employer, no account, unsubscribe in one click.
Site address
8046 REZANOF DRIVE KODIAK TERMINAL
City
KODIAK
State
AK
ZIP
99615
Mailing
8046 REZANOF DRIVE, KODIAK, AK 99615
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488320
Employees
12
Ownership type
A

9 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 1 1 instance 12 exposed
Issued
Penalty
Initial $3604.00 · Current $1802.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).    Maintenance Shop Bay 1, left -hand side, outer entrance, on or about 19 September 2018 and times prior thereto; an energized electrical wires were not guarded against accidental contact. An energized exterior wiring bundle was missing an approved enclosure. This condition exposed employee to electrical shock and electrical burn hazards.
Recent events (2)
  • — I (S) $1802
  • — Z (S) $3604

1910.305 B02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  Maintenance Shop, Bay 2 West wall, on or about 19 September 2018 and times prior thereto; an energized two-place 120 volt electrical outlet did not have the faceplate installed. This condition exposed employees to an electrical shock and electrical burn hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 A02

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4240.00 · Current $2120.00 Reduced
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity.    Maintenance Shop Bay 1, East Wall, adjacent to 250-gallon work dock; on or about 19 September 2018 and times prior thereto; a two place 120-volt energized electrical outlet had reverse polarity. This condition exposed employees to an electrical shock and electrical burn hazards.
Recent events (2)
  • — I (S) $2120
  • — Z (S) $4240

1910.305 G01 IV A

Serious Gravity 1 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $4240.00 · Current $2120.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.    Maintenance Shop, Bay 2, East wall; on or about 19 September 2018 and times prior thereto; two instances were noted where flexible cords were used in lieu of fixed wiring:         a)  A blue medium-duty extension cord, length unknown, was attached to the wall and routed to supply power to a AIWA stereo set, serial number unknown.         b)  A orange medium-duty extension cord was attached to the wall and routed to provide a power source to a Kenmore washing machine, serial number unknown.    This condition exposed employees to an electrical shock and electrical burns hazard.
Recent events (2)
  • — I (S) $2120
  • — Z (S) $4240

1910.334 A02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  Maintenance Shop, Bay 2, workbench adjacent to stanchion; on or about 19 September 2018 and time prior there to; the employer did not ensure that portable cord and plug equipment was inspected prior to use. An energized orange 50-foot medium duty extension cord had damaged to the outer protective jack. A Mikata Model 90058, 5-inch Angle Grinder, Serial number 2340114A was plugged into the extension cord. This condition exposed employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1917.156 A09

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $3604.00 · Current $1802.00 Reduced
29 CFR 1917.156(a)(9): Liquid fuel dispensing devices, such as pumps, were not mounted on a concrete island or otherwise protected against collision damage.    Maintenance Shop, adjacent to Bay 2; on or about 19 September 2018 and times prior thereto, a 500-gallon flammable fuel tank was not protected from vehicular traffic. Fuel tank is located adjacent to a moderate vehicular traffic area. This tank supplies fuel for the hot water heater. This condition exposed employees to fire and explosion hazards.
Recent events (2)
  • — I (S) $1802
  • — Z (S) $3604

1910.305 G01 IV B

Repeat Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $9977.00 · Current $4988.00 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors.    Maintenance Shop, Bay 2, East wall; on or about 19 September 2018 and times prior thereto; a blue medium-duty extension cord, length unknown, was routed through a wall opening to provide power to a AIWA stereo set, serial number unknown. This condition exposed employees to an electrical shock and electrical burns hazard.    Samson Tug and Barge Company, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(B), which was contained in OSHA inspection number 981120, citation number 1, item number 1 and was affirmed as a final order on 06 July 2014, with respect to a workplace located at Samson Tug and Barge Company, 3311 Tongass Ave. Ketchikan, AK.
Recent events (2)
  • — I (R) $4988
  • — Z (R) $9977

1903.2 A01

Deleted Other-than-serious 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $793.00 · Current $0.00 Reduced
29 CFR 1903.2(a)(1): The employer did not post and keep posted OSHA notices informing employees of the protections and obligations provided for in the Act, and that for assistance and information, including copies of the Act and of specific safety and health standards.  Kodiak Terminal, Administrative office; on or about 19 September 2018 and times prior thereto; the employer did not post the OSHA poster informing employees of the protections and obligations provided by the Act. This condition exposed employees to inadequate work practices.
Recent events (2)
  • — I (O) $0
  • — Z (O) $793

1904.32 A01

Other-than-serious 1 instance 145 exposed
Issued
Abate by
Penalty
Initial $1414.00 · Current $707.00 Reduced
29 CFR 1904.32(a)(1): A review of the OSHA Log of Recordable Work-Related Injuries and Illnesses (OSHA Form 300 or equivalent) was not completed to ensure the Log was accurate and complete, and/or deficiencies were not identified and corrected at the end of each calendar year.    Administrative Office; on or about 19 September 2018 and times prior thereto; the employer did not ensure that the Summary of Work-Related Injuries and Illnesses (OSHA Form 300A) were complete and accurate. On the 2017 OSHA Form 300A, the Total Recordable Cases (65) is different from Total of Injuries and Illnesses (9). The average number of employees (9) and total hours worked (191,152) exceeds total hours in a calendar year (8,760).This condition leads to inaccurate reporting of injuries and illnesses.
Recent events (2)
  • — I (O) $707
  • — Z (O) $1414

View SAMSON TUG AND BARGE, INC.'s full OSHA safety record →