Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: SAMSON TUG AND BARGE, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SAMSON TUG AND BARGE, INC. in PIER 2 & 8046 REZANOF DR., KODIAK, AK 99615 (NAICS 488320). OSHA activity number 344994157.

Watch Samson TUG AND Barge, INC. — free Get an email when a new federal OSHA severe-injury report for Samson TUG AND Barge, INC. is published. One employer, no account, unsubscribe in one click.
Site address
PIER 2 & 8046 REZANOF DR.
City
KODIAK
State
AK
ZIP
99615
Mailing
8046 REZANOF DRIVE, KODIAK, AK 99615
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488320
Employees
110
Ownership type
A

2 citations on file for this inspection.

1910.303 G01 II

Serious Gravity 5 1 instance 11 exposed
Issued
Abate by
Penalty
Initial $7724.00 · Current $4634.00 Reduced
29 CFR  1910.303(g)(1)(ii):  The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a)  East Bay Maintenance Shop - on or about October 22, 2020, employees performed maintenance operations in the east bay, but electrical Panel A was not provided sufficient working space with the area used for placement and storage of a washing machine, exposing employees to fire hazards.   b)  West Bay Maintenance Shop - on or about October 22, 2020, employees performed maintenance operations in the west bay, but electrical Panel B was not provided sufficient working space with the area used for placement and storage of metal parts storage rack, exposing employees to fire hazards.
Recent events (2)
  • — I (S) $4634
  • — Z (S) $7724

1910.305 G01 IV A

Repeat Gravity 5 1 instance 11 exposed
Issued
Abate by
Penalty
Initial $15448.00 · Current $9269.00 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) West Bay Maintenance Shop - on or about October 22, 2020, the employer had installed a hot water heater with the use of flexible extension cords substituted for permanent wiring, exposing employees to electrical and fire hazards.  Samson Tug & Barge, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 1347595, citation number 1, item 3a and was affirmed as a final order on October 30, 2019, with respect to a workplace located at 8046 Rezanof Drive in Kodiak, Alaska.
Recent events (2)
  • — I (R) $9269
  • — Z (R) $15448

View SAMSON TUG AND BARGE, INC.'s full OSHA safety record →