OSHA Inspection: INTERMOUNTAIN ELECTRIC SERVICE, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of INTERMOUNTAIN ELECTRIC SERVICE, INC. in 325 FORTUNE ROAD, PAGOSA SPRINGS, CO 81147 (NAICS 238210). OSHA activity number 343476750.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Intermountain Electric Service, INC. — free Get an email when a new federal OSHA severe-injury report for Intermountain Electric Service, INC. is published. One employer, no account, unsubscribe in one click.
Site address
325 FORTUNE ROAD
City
PAGOSA SPRINGS
State
CO
ZIP
81147
Mailing
85 PURPLE SAGE DRIVE, ROCK SPRINGS, WY 82901
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

2 citations on file for this inspection.

1926.950 B02 V

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Nov 5, 2018
Abate by
Dec 3, 2018
Penalty
Initial $9,054 · Current $0 Reduced
29 CFR 1926.950(b)(2)(v): The employer did not ensure each qualified employee was trained and competent in the recognition of electrical hazards to which the employees may be exposed and the skills and techniques necessary to control or avoid these hazards:  1) On September 1, 2018, employees were exposed to shock and electrocution hazards due to working near energized 7,200 volt equipment inside a switch box.  Employees did not have training and knowledge necessary to control or avoid the hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9054

1926.961 C02

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 5, 2018
Abate by
Dec 3, 2018
Penalty
Initial $0 · Current $9,054
29 CFR 1926.961(c)(2): The employer did not ensure that all switches, dis-connectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be de-energized are open and the employer did not render such means inoperable, unless its design does not so permit, and then ensure that such means are tagged to indicate that employees are at work:    1) On September 1, 2018, employees were exposed to shock and electrocution hazards and were not required by the employer to de-energize the 7,200 volt electrical equipment inside a switch box prior to working on or near it.