Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BAY ELECTRIC COMPANY INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BAY ELECTRIC COMPANY INC. in NASA LANGLEY, HAMPTON, VA 23666 (NAICS 238210). OSHA activity number 343498739.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch BAY Electric Company INC. — free Get an email when a new federal OSHA severe-injury report for BAY Electric Company INC. is published. One employer, no account, unsubscribe in one click.
Site address
NASA LANGLEY
City
HAMPTON
State
VA
ZIP
23666
Mailing
627 36TH STREET, NEWPORT NEWS, VA 23607
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
80
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Other-than-serious 1 instance 30 exposed
Issued
Nov 7, 2018
Abate by
Dec 5, 2018
Penalty
Initial $3,297 · Current $1,500 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a)    NASA Langley: On or about 09/27/2018, junction boxes used for enclosed spliced wiring for string lights were not used according to its listing in that the boxes were not mounted thereby exposing employees to a possible shock hazard.   Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $1500
  • — Z (S) $3297

1926.404 F07 I

Other-than-serious 1 instance 30 exposed
Issued
Nov 7, 2018
Abate by
Dec 5, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(7)(i): Metal cable trays, metal raceways, or metal enclosures for conductors were not grounded and such assemblies did not meet the exceptions described in subparagraphs [A] and [B]:  a)    NASA Langley: On or about 09/27/2018, three-wire temporary string lights, splices enclosed in a metal junction box and hung from the overhead was not grounded to protect employees from a possible electric shock.   Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View BAY Electric Company INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343498739.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.