OSHA Inspection: CARFAIR COMPOSITES USA INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CARFAIR COMPOSITES USA INC in 431 E MAIN STREET, GILLETT, WI 54124 (NAICS 336211). OSHA activity number 343501722.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Carfair Composites USA INC — free Get an email when a new federal OSHA severe-injury report for Carfair Composites USA INC is published. One employer, no account, unsubscribe in one click.
Site address
431 E MAIN STREET
City
GILLETT
State
WI
ZIP
54124
Mailing
431 E MAIN STREET, GILLETT, WI 54124
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336211
Employees
54
Ownership type
A

6 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 6 exposed
Issued
Jan 18, 2019
Abate by
Feb 26, 2019
Penalty
Initial $8,638 · Current $4,319 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a)    On or about 10/3/2018, Employer was using a relocatable power tap without having it plugged directly into a permanently installed receptacle creating a fire/burn hazard for employees.    b)    On or about 10/3/2018, Employer was using a metal electrical handy box on the end of a flexible cord to make a home made extension cord creating an electrocution hazard for employees.
Recent events (2)
  • — I (S) $4319
  • — Z (S) $8638

1910.303 B07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Feb 26, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused opening in electrical cabinets were not effectively closed provide substantially equivalent protection to the equipment:   a)    On or about 10/3/2018, Employer was using a disconnect with a missing knockout plug on the side of the box. creating an electrical arc hazard as shown with the paint on the side of the box.  b)    On or about 10/3/2018, Employer was using an electrical outlet box at the ceiling that was missing a knockout plug.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 6 instances 6 exposed
Issued
Jan 18, 2019
Abate by
Feb 26, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)    On or about 10/3/2018, Company was using multiple flexible cords as permanent wiring in the 500 ton press area creating an electrical shock hazard for employees.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Feb 26, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:   a)    On or about 10/3/2018, Employer was using a flexible electrical cord without strain relief at the plug creating an electrical shock hazard for employees.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 51 exposed
Issued
Jan 18, 2019
Abate by
Feb 26, 2019
Penalty
Initial $6,911 · Current $3,456 Reduced
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    a)    On or about 10/3/2018, Employer had not developed a written Hazard communication program for their employees which were handling hazardous chemicals like RC ACETONE.
Recent events (2)
  • — I (S) $3455.5
  • — Z (S) $6911

1910.1200 F10

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 18, 2019
Abate by
Jan 29, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(10): The employer did not ensure that workplace labels or other forms of warnings were prominently displayed on the container or readily available in the work area throughout each work shift:    a)    On or about 10/3/2018, Employer was missing workplace labels on hazardous chemicals which their employees were handling, creating an over exposure hazard for chemicals like RC ACETONE.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Carfair Composites USA INC's full OSHA safety record →