LA PLACE, LA —
OSHA Inspection: BD LAPLACE, LLC
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of BD LAPLACE, LLC in 138 HIGHWAY 3217, LA PLACE, LA 70068 (NAICS 331110). OSHA activity number 343513206.
Where did this inspection happen?
- Establishment
- BD LAPLACE, LLC
- Site address
- 138 HIGHWAY 3217
- City
- LA PLACE
- State
- LA
- ZIP
- 70068
- Mailing
- 138 HIGHWAY 3217, LA PLACE, LA 70068
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331110
- Employees
- 366
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.253 B02 IV
- Issued
- Abate by
- Penalty
- Initial $7577.00 · Current $4546.00 Reduced
General-duty citation text
29 CFR 1910.253(b)(2)(iv): Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use. a) On or about October 02, 2018, in the Quality Control Area, the employer failed to provide valve protection caps for O2 pressurized cylinders & compressed gas cylinders.
Recent events (2)
- — I (S) $4546.2
- — Z (S) $7577
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $5683.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. a) On or about October 02, 2018, in the Electrical Maintenance Shop the employer failed to label breakers in an open electrical panel box. b) On or about October 02, 2018, in the Label Bricking Stand Area, the employer failed to label breakers in an open electrical panel box.
Recent events (2)
- — I (S) $5683.2
- — Z (S) $9472
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $7577.00 · Current $4546.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage. a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from using working space around electrical equipment as a storage area for light bulbs.
Recent events (2)
- — I (S) $4546.2
- — Z (S) $7577
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $5683.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i). a) On or about October 02, 2018 in the Electrical Maintenance shop, the employer failed to prevent employees from working near an opened electrical panel box that did not have a dead front cover.
Recent events (2)
- — I (S) $5683.2
- — Z (S) $9472
1910.305 B01 I
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $5683.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed. a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from working near an open electrical box, that had exposed screws and live electrical lines.
Recent events (2)
- — I (S) $5683.2
- — Z (S) $9472
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $9472.00 · Current $5683.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from working near a open electrical box with live wires that were not covered/protected, by a panel blank.
Recent events (2)
- — I (S) $5683.2
- — Z (S) $9472
1910.303 E01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary. a) On or about October 02, 2018 in the Label Bricking Stand Area, the employer failed to prevent employees from working near a electrical panel box without having any signage or markings on it.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. a) On or about October 02, 2018, in the Electrical Maintenance Shop, the employer failed to prevent employees from utilizing a work table that had an electrical power source with inadequate strain relief. b) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from operating a Porter-Cable band saw #725 with inadequate strain relief.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 331110)
CANTON, OH—2026-07-09
METALLUS, INC.
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
PITTSBORO, IN—2026-07-06
STEEL DYNAMICS, INC.
PELHAM, AL—2026-06-30
VULCAN STEEL PRODUCTS INC
BLASDELL, NY—2026-06-26
FRONTIER STEEL
More inspections in LA
AMELIA, LA—2026-07-10
CONRAD SHIPYARD, LLC
MORGAN CITY, LA—2026-07-10
G4 SERVICES LLC
PIERRE PART, LA—2026-07-08
DOLLAR GENERAL
LAKE CHARLES, LA—2026-07-01
GULF COAST FORENSIC SOLUTIONS
BATON ROUGE, LA—2026-06-26
TRAFFIC CONTROL PRODUCTS CO. OF LOUISIANA, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343513206.