1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: BD LAPLACE, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of BD LAPLACE, LLC in 138 HIGHWAY 3217, LA PLACE, LA 70068 (NAICS 331110). OSHA activity number 343513206.

Watch BD Laplace, LLC — free Get an email when a new federal OSHA severe-injury report for BD Laplace, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
BD LAPLACE, LLC
Site address
138 HIGHWAY 3217
City
LA PLACE
State
LA
ZIP
70068
Mailing
138 HIGHWAY 3217, LA PLACE, LA 70068
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331110
Employees
366
Ownership type
A

8 citations on file for this inspection.

1910.253 B02 IV

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $7577.00 · Current $4546.00 Reduced
29 CFR 1910.253(b)(2)(iv): Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use.  a) On or about October 02, 2018, in the Quality Control Area, the employer failed to provide valve protection caps for O2 pressurized cylinders & compressed gas cylinders.
Recent events (2)
  • — I (S) $4546.2
  • — Z (S) $7577

1910.303 F02

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $5683.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.  a) On or about October 02, 2018, in the Electrical Maintenance Shop the employer failed to label breakers in an open electrical panel box.  b) On or about October 02, 2018, in the Label Bricking Stand Area, the employer failed to label breakers in an open electrical panel box.
Recent events (2)
  • — I (S) $5683.2
  • — Z (S) $9472

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $7577.00 · Current $4546.00 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from using working space around electrical equipment as a storage area for light bulbs.
Recent events (2)
  • — I (S) $4546.2
  • — Z (S) $7577

1910.303 G02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $5683.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).  a) On or about October 02, 2018 in the Electrical Maintenance shop, the employer failed to prevent employees from working  near an opened electrical panel box that did not have a dead front cover.
Recent events (2)
  • — I (S) $5683.2
  • — Z (S) $9472

1910.305 B01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $5683.00 Reduced
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed.  a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from working near an open electrical box,  that had exposed screws and live electrical lines.
Recent events (2)
  • — I (S) $5683.2
  • — Z (S) $9472

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9472.00 · Current $5683.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  a) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from working  near a open electrical box with live wires that were not covered/protected, by a panel blank.
Recent events (2)
  • — I (S) $5683.2
  • — Z (S) $9472

1910.303 E01 II

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary.  a) On or about October 02, 2018 in the Label Bricking Stand Area, the employer failed to prevent employees from working near a electrical panel box without having any signage or markings on it.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.  a) On or about October 02, 2018, in the Electrical Maintenance Shop, the employer failed to prevent employees from utilizing a work table that had an electrical power source with inadequate strain relief.   b) On or about October 02, 2018 in the Electrical Maintenance Shop, the employer failed to prevent employees from operating a Porter-Cable band saw #725 with inadequate strain relief.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343513206.