OSHA Inspection: CUSTOM FIBERGLASS PRODUCTS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CUSTOM FIBERGLASS PRODUCTS, INC. in 110 PETROCHEM DRIVE, MINDEN, LA 71058 (NAICS 238990). OSHA activity number 343521449.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Custom Fiberglass Products, INC. — free Get an email when a new federal OSHA severe-injury report for Custom Fiberglass Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
110 PETROCHEM DRIVE
City
MINDEN
State
LA
ZIP
71058
Mailing
110 PETROCHEM DRIVE, MINDEN, LA 71058
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238990
Employees
14
Ownership type
A

7 citations on file for this inspection.

1910.106 D05 I

Serious Gravity 5 2 instances 9 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $3,696 · Current $1,478 Reduced
29 CFR 1910.106(d)(5)(i): "Egress." flammable liquids, including stock for sale, were stored in a location that limited the use of exits, stairways, or areas normally used for the safe egress of people.    On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to store 55 gallon drums of acetone and other class 3 flammable liquids next to and blocking egress points from the building.    Instance 1: 55 gallon drum of acetone in the middle of bay door closest to office trailer.    Instance 2: west side bay door has large pile of flammable liquids stored next to egress point
Recent events (2)
  • — I (S) $1478.4
  • — Z (S) $3696

1910.106 D05 V

Serious Gravity 5 1 instance 14 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(5)(v):  Flammable liquid storage was not in a portion of the building cut off by a standard fire wall:  On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to store large quantities of various class 3 flammable liquids in a pile and on shelves located next to the west side bay door of the shop. A large number of containers and quantity of flammable liquids was observed piled in an area next to the door in a wide open area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 D05 VI E

Serious Gravity 5 1 instance 14 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(5)(vi)(e): Piles were closer than 3 feet to the nearest beam, chord, girder, or other obstruction:  On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to store large quantities of various class 3 flammable liquids in a pile and on shelves located next to the west side bay door of the shop. A large number of containers and quantity of flammable liquids was observed piled in an area next to the door in a wide open area. This includes next to the support beams and wall of the warehouse.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E06

Serious Gravity 10 1 instance 14 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $5,174 · Current $2,070 Reduced
29 CFR 1910.106(e)(6): In locations where flammable vapors may have been present, precautions were not taken to prevent ignition by eliminating or controlling sources of ignition such as but not limited to open flames, lightning, smoking, cutting and welding, hot surfaces, frictional heat, sparks (static, electrical, and mechanical), spontaneous ignition, chemical and physical-chemical reactions, and radiant heat:    On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to Use electric sanders in close proximity to 55 gallon drums of acetone.
Recent events (2)
  • — I (S) $2069.6
  • — Z (S) $5174

1910.106 E06 II

Serious Gravity 5 1 instance 14 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii): Class III flammable liquid(s) were dispensed into containers without electrically interconnecting the nozzle and the container:  On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to transfer acetone from a horizontally stored 55 gallon drum to smaller plastic and metal containers without grounding or bonding systems.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 2 instances 14 exposed
Issued
Dec 10, 2018
Penalty
Initial $2,513 · Current $1,005 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to Use electric extension cords and electric powered fan that had power cords with stress damage to the plug.     Instance 1: Extension cord attached to orbital sander west side shop area.    Instance 2: Box fan north bay door area hard wire to power switch  junction box.
Recent events (2)
  • — I (S) $1005.2
  • — Z (S) $2513

1910.106 E02 II B 2

Serious Gravity 10 1 instance 14 exposed
Issued
Dec 10, 2018
Abate by
Dec 28, 2018
Penalty
Initial $5,174 · Current $2,070 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(2): 120 gallons of Category 2, 3, or 4 flammable liquids in containers.    On or about October 10, 2018, in the fabrication shop at 110 Petrochem Drive Minden, LA, the Employer allowed employees to store quantities exceeding 400 gallons of class 3 flammable liquids throughout the shop floor and not in proper designated storage areas.
Recent events (2)
  • — I (S) $2069.6
  • — Z (S) $5174

View Custom Fiberglass Products, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343521449.