BOLLING AFB, DC —
OSHA Inspection: AIREKO ENERGY U.S., LLC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AIREKO ENERGY U.S., LLC. in BUILDING 363, REAR PARKING LOT, BOLLING AFB, DC 20032 (NAICS 238210). OSHA activity number 343526414.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AIREKO ENERGY U.S., LLC.
- Site address
- BUILDING 363, REAR PARKING LOT
- City
- BOLLING AFB
- State
- DC
- ZIP
- 20032
- Mailing
- 2415 SAND LAKE ROAD, SUITE E, ORLANDO, FL 32809
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 57
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.416 A01
- Issued
- Mar 21, 2019
- Abate by
- Mar 27, 2019
- Penalty
- Initial $9,282 · Current $9,282
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a) Solar Pad #26, Meter Cabinet - An employee entered into an energized meter cabinet to install additional wiring and received burns when an arc flash occurred, 13,200 volt service, on or about 09/28/2018. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification. This documentation may include, but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (3)
- — F (O) $9282
- — C (S) $9282
- — Z (S) $9282
1926.416 A03
- Issued
- Mar 21, 2019
- Abate by
- Mar 27, 2019
- Penalty
- Initial $9,282 · Current $9,282
General-duty citation text
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into pysical or electrical contact with the electric power circuit: a) Solar Pad #26, Meter Cabinet - An electrician entered into an electrical meter cabinet to install wiring and the service within the cabinet was not determined to be de-energized, which caused the electrician to get to close to an energized live part where an arc flash occurred, 13,200 volt service, on or about 09/28/2018. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification. This documentation may include, but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (3)
- — F (S) $9282
- — C (S) $9282
- — Z (S) $9282
1926.417 A
- Issued
- Mar 21, 2019
- Abate by
- Mar 27, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged: a) Solar Pad #26 and #34 Transformers - An employee was installing new grounds on the secondary side of four transformers and the selector switches which de-energized the service were not provided with a tag, 277/480 volt service, on or about 09/28/2018. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet).
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 238210)
More inspections in DC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343526414.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.