OSHA Inspection: D&D POWER, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of D&D POWER, LLC in 179 MOORES HILL ROAD, NEW WINDSOR, NY 12553 (NAICS 541990). OSHA activity number 343537213.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch D&D Power, LLC — free Get an email when a new federal OSHA severe-injury report for D&D Power, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
D&D POWER, LLC
Site address
179 MOORES HILL ROAD
City
NEW WINDSOR
State
NY
ZIP
12553
Mailing
16 HEMLOCK DRIVE, LATHAM, NY 12110
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
90
Ownership type
A

1 citation on file for this inspection.

1910.269 L08 V D

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Mar 12, 2019
Abate by
Mar 18, 2019
Penalty
Initial $9,282 · Current $0 Reduced
29 CFR 1910.269(l)(8)(v)(D): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective equipment consisting of at a minimum a face shield with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2 but less than 9.0 Cal/cm2.     a) On or about October 15, 2018, at 179 Moore Hill Road, New Windsor, NY, a lineman employee who was installing a new pole, connected an energized transformer line to the wrong energized line resulting in an arc flash explosion. Employee was not wearing face protection and was exposed to a heat energy level of 4.0 Cal/cm2.