OSHA Inspection: REVEL NAIL LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of REVEL NAIL LLC. in 90 COLES RD, BLACKWOOD, NJ 08012 (NAICS 325620). OSHA activity number 343550075.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Revel Nail LLC. — free Get an email when a new federal OSHA severe-injury report for Revel Nail LLC. is published. One employer, no account, unsubscribe in one click.
Establishment
REVEL NAIL LLC.
Site address
90 COLES RD
City
BLACKWOOD
State
NJ
ZIP
08012
Mailing
90 COLES RD, BLACKWOOD, NJ 08012
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325620
Employees
85
Ownership type
A

5 citations on file for this inspection.

1910.242 B

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $5,174 · Current $2,000 Reduced
29 CFR 1910.242(b): Compressed air, that was not reduced to less than 30 p.s.i., was used for cleaning purposes without effective chip guarding and personal protective equipment.    a)  Revel Nail LLC. - Blending area: Compressed air was approximately 100 psi and it was used to clean the area and employees clean off themselves and their clothing, on or about 10/02/2018.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $5174

1910.304 B03

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $5,174 · Current $2,000 Reduced
29 CFR 1910.304(b)(3): Ground-fault circuit interrupter was not installed for the protection of personnel.    a) Revel Nail LLC.- Wash Room:  The outlets located in the wash room area did not have a Ground-Fault Circuit Interrupter (GFCI) to protect employees from electrical hazards while becoming in contact with wet or damp surfaces, observed on or about 10/02/2018.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $5174

1910.305 J02 VI

Serious Gravity 5 1 instance 2 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(vi): A receptacle installed in a wet location where the product intended to be plugged into it was not to be attended while in use did not have an enclosure that was weatherproof with the attachment plug cap inserted or removed:  a)  Revel Nail LLC.- Wash Room:  The outlets located in the wash room area did not have a cover to protect them against water or other liquids present around the area, the employees are exposed to electrical hazards while coming in contact with wet or damp surfaces.  Observed on or about 10/02/2018.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $3,880 · Current $2,000 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a)  Revel Nail LLC. - throughout the manufacturing plant: Multiple extension cords were used for prolonged periods of time to power small equipment and machines such as vacuums, etc., observed on or about 10/02/2018.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3880

1910.1200 F05 I

Other-than-serious 1 instance 3 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein:  a) Revel Nail LLC. - packing and blending area: Plastic bottles and containers containing an unknown chemical were not labeled, observed on or about 10/02/2018.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0