OSHA Inspection: COONROD ELECTRIC CO., LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of COONROD ELECTRIC CO., LLC in ORYX LEASE TANK BATTERY/PYOTE TRUCK STATION 3 MILES WEST OF PYOTE, TX OFF HWY 2355, PYOTE, TX 79777 (NAICS 238210). OSHA activity number 343565933.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Coonrod Electric CO., LLC for free Get an email when a new federal OSHA severe-injury report for Coonrod Electric CO., LLC is published. One employer, no account, unsubscribe in one click.
Site address
ORYX LEASE TANK BATTERY/PYOTE TRUCK STATION 3 MILES WEST OF PYOTE, TX OFF HWY 2355
City
PYOTE
State
TX
ZIP
79777
Mailing
224 N. RACHAL ST., SINTON, TX 78387
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
256
Ownership type
Private (A)

5 citations on file for this inspection.

1910.147 C04 II D

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Feb 1, 2019
Abate by
Feb 28, 2019
Penalty
Initial $13,260 · Current $0 Reduced
29 CFR 1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control.   On or about October 25, 2018, in the VFD Building at the Oryx Lease/Pyote Truck Station off Hwy 2355, employees were exposed to electrical arc flash hazards as the employer failed to verify the effectiveness of lock out devices and did not ensure that all components had been tested and locked out with energy control measures before allowing employees to work on reconnecting electrical cables.
Recent events (2)
  • · I (S) $0
  • · Z (S) $13260

1910.333 B02 II A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Feb 1, 2019
Abate by
Feb 28, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(ii)(A): Safe procedures for deenergizing circuits and equipment were not determined before circuits and equipment were de-energized.  On or about October 25, 2018, at the Oryx Lease/Pyote Truck Station off Hwy 2355, employees were exposed to electrical arc flash hazards while reconnecting electrical cables in a VFD Electrical Building without properly verifying that all components had been deenergized.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.333 B02 IV

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 1, 2019
Abate by
Feb 28, 2019
Penalty
Initial $0 · Current $8,964
29 CFR 1910.333(b)(2)(iv): The employer did not properly verify if the components were positively de energized or in an otherwise safe condition to protect the employees from an electrical shock hazard.    On or about October 25, 2018, at the Oryx Lease/Pyote Truck Station off Hwy 2355, employees were exposed to electrical arc flash hazards while reconnecting electrical cables in a VFD Electrical Building without properly verifying that all components had been deenergized.
Recent events (2)
  • · I (S) $8964.48
  • · Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 1, 2019
Abate by
Feb 28, 2019
Penalty
Initial $13,260 · Current $7,901 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.    On or about October 25, 2018, at the Oryx Lease/Pyote Truck Station off Hwy 2355, employees were exposed to electrical arc flash hazards in excess of 4160 volts without using the type 1 required electrical personal protection equipment.
Recent events (2)
  • · I (S) $7901.47
  • · Z (S) $13260

1910.1200 H01

Other-than-serious 1 instance 1 exposed
Issued
Feb 1, 2019
Abate by
Feb 28, 2019
Penalty
Initial $1,063 · Current $1,063
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area.   On or about October 25, 2018, at the Oryx Lease/Pyote Truck Station off Hwy 2355, employees were exposed to inhalation hazards from not having current H2S certifications.