Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: YOSEMITE HOSPITALITY, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of YOSEMITE HOSPITALITY, LLC in 9001VILLAGE DRIVE, YOSEMITE NATIONAL PARK, CA 95389 (NAICS 561210). OSHA activity number 343573226.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Yosemite Hospitality, LLC — free Get an email when a new federal OSHA severe-injury report for Yosemite Hospitality, LLC is published. One employer, no account, unsubscribe in one click.
Site address
9001VILLAGE DRIVE
City
YOSEMITE NATIONAL PARK
State
CA
ZIP
95389
Mailing
9001VILLAGE DRIVE, YOSEMITE NATIONAL PARK, CA 95389
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
1450
Ownership type
A

9 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 4 instances 4 exposed
Issued
Nov 8, 2018
Abate by
Dec 6, 2018
Penalty
Initial $7,853 · Current $5,890 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, in-going nip points, rotating parts, flying chips and sparks:   Facility Maintenance Shops: In the following locations, the employer did not provide point of operation and rotating parts guards. Employees were exposed to severe lacerations and amputations.   1) Wood Shop: A Delta Rockwell 10 inch table saw and a Delta Milwaukee Radial saw were not provided with guards to protect the operator from hazards created by point of operation.  2) Auto Maintenance Garage: A Sears / Craftsman 20" drill press was not provided with a guard to protect employees from flying chips and sparks.  3) Machine Shop: A Dayton 15" drill press was not provided with a guard to protect employees from flying chips and sparks.
Recent events (2)
  • — I (S) $5889.75
  • — Z (S) $7853

1910.303 B02

Serious Gravity 1 2 instances 8 exposed
Issued
Nov 8, 2018
Penalty
Initial $4,005 · Current $3,004 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listed or labeling:    In the following locations two metal receptacle boxes with knockouts, designed for fixed installation, were wired with a flexible cord were not securely affixed to any surface and were used as extension cords:  1)  Plumbing Shop: The 4 inch square metal electrical box with knockouts attached to the end of black flexible cord and plug, was not listed, labeled or certified for this application.  2)  Electrical / Refrigeration Shop: The 4 inch square metal electrical box with knockouts attached to the end of yellow retractable flexible cord and plug, was not listed, labeled or certified for this application.
Recent events (2)
  • — I (S) $3003.75
  • — Z (S) $4005

1910.37 A03

Other-than-serious 1 instance 1 exposed
Issued
Nov 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit routes were not free and unobstructed. Materials or equipment were placed, either permanently or temporarily, within the exit route.   Facility Automotive Garage, Parts Storage Room: The designated exit door located in the Parts Storage room was blocked from the outside with sand bags.  Employees were exposed to entrapment hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.37 B02

Other-than-serious 1 instance 1 exposed
Issued
Nov 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "EXIT":  Facility Maintenance Shop, Storage and Uniform shop: The main hallway door to the outside from the storage room was designated as an exit door and was not marked with a sign reading "EXIT".
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.212 B

Other-than-serious 1 instance 3 exposed
Issued
Nov 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  Facility Maintenance Shops, Machine Shop: The Dayton 15 inch drill press was not anchored to prevent moving or tipping over.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.215 B09

Other-than-serious 2 instances 2 exposed
Issued
Nov 8, 2018
Abate by
Dec 6, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one-fourth inch:  In the following locations, two 10 inch bench grinders had the distance between the abrasive wheel periphery and the adjustable tongue guard not adjusted to the maximum permitted opening of one fourth inch.  1) Facility Maintenance Machine Shop: A Thor bench grinder tongue guard was measured one inch and a quarter of an inch from the abrasive wheel.   2) Automotive Garage: A Dayton bench grinder tongue guard was measured two inches and a quarter of an inch from the abrasive wheel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01

Other-than-serious 2 instances 2 exposed
Issued
Nov 8, 2018
Abate by
Dec 6, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    In the following locations, two electrical panels were blocked by storage exposing employees to electrical hazards in case of quick disconnect is required:  1) Maintenance Facility Storage Room  2) Garage Storage Room
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.304 G05

Other-than-serious 1 instance 2 exposed
Issued
Nov 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  Facility Maintenance Shops: Two industrial pedestal fans power supply cords were missing its ground prongs.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 II

Other-than-serious 2 instances 2 exposed
Issued
Nov 8, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   Unused openings in two electrical panels were not effectively closed due to missing circuit brakes in the following locations:  1) Maintenance Facility Storage Room electrical panel "I"  2) Kitchen Dish Washing Room electrical panel "C 2"
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Yosemite Hospitality, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343573226.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.