OSHA Inspection: DIVERSITY-VUTEQ LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DIVERSITY-VUTEQ LLC in 2300 MUNSFORD DRIVE, NEW ALBANY, MS 38652 (NAICS 326199). OSHA activity number 343576294.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Diversity-Vuteq LLC — free Get an email when a new federal OSHA severe-injury report for Diversity-Vuteq LLC is published. One employer, no account, unsubscribe in one click.
Establishment
DIVERSITY-VUTEQ LLC
Site address
2300 MUNSFORD DRIVE
City
NEW ALBANY
State
MS
ZIP
38652
Mailing
2300 MUNSFORD DRIVE, NEW ALBANY, MS 38652
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
151
Ownership type
A

6 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 12, 2018
Abate by
Dec 28, 2018
Penalty
Initial $7,853 · Current $4,712 Reduced
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.  (a) Injection Molder 2200 - On or about November 01, 2018 an electrical outlet box designed to be mounted at a fixed location was being used as an extension cord.
Recent events (2)
  • — I (S) $4711.8
  • — Z (S) $7853

1910.305 B01 II

Serious Gravity 5 3 instances 3 exposed
Issued
Dec 12, 2018
Abate by
Dec 28, 2018
Penalty
Initial $7,853 · Current $4,712 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  (a) Injection Molding - On or about November 01, 2018 unused openings on 480 volt 3 phase electrical outlet boxes were not closed.  - Injection Molder 390 - Injection Molder 950-1 - Injection Molder 2200
Recent events (2)
  • — I (S) $4711.8
  • — Z (S) $7853

1910.305 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 12, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.  (a) Injection mold 950-2 - On or about November 01, 2018 480 volt 3 phase outlet box was missing the cover plate.  -  Injection Molder 950-2 -  Injection Molder110
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07

Other-than-serious 1 instance 2 exposed
Issued
Dec 12, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7): 29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner.  (a) Hazmat Area - On or about November 01, 2018 energized 208 volt single phase temporary flexible conductor was not installed in a neat and workmanlike manner.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 I

Other-than-serious 1 instance 3 exposed
Issued
Dec 12, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.  (a) Hazmat Area - On or about November 01, 2018 energized 208 volt single phase temporary flexible conductor was not protected from abrasion.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 2 instances 3 exposed
Issued
Dec 12, 2018
Abate by
Dec 28, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to the joints or terminal screws:  (a)  Injection Molding - On or about November 01, 2018 the outer sheathing was not connected to the strain relief connector.   - No. 67 Thermulator - Injection Molder 2800
Recent events (2)
  • — I (O) $0
  • — Z (O) $0