NEW ALBANY, MS —
OSHA Inspection: DIVERSITY-VUTEQ LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DIVERSITY-VUTEQ LLC in 2300 MUNSFORD DRIVE, NEW ALBANY, MS 38652 (NAICS 326199). OSHA activity number 343576294.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DIVERSITY-VUTEQ LLC
- Site address
- 2300 MUNSFORD DRIVE
- City
- NEW ALBANY
- State
- MS
- ZIP
- 38652
- Mailing
- 2300 MUNSFORD DRIVE, NEW ALBANY, MS 38652
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 151
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B02
- Issued
- Dec 12, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $7,853 · Current $4,712 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. (a) Injection Molder 2200 - On or about November 01, 2018 an electrical outlet box designed to be mounted at a fixed location was being used as an extension cord.
Recent events (2)
- — I (S) $4711.8
- — Z (S) $7853
1910.305 B01 II
- Issued
- Dec 12, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $7,853 · Current $4,712 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. (a) Injection Molding - On or about November 01, 2018 unused openings on 480 volt 3 phase electrical outlet boxes were not closed. - Injection Molder 390 - Injection Molder 950-1 - Injection Molder 2200
Recent events (2)
- — I (S) $4711.8
- — Z (S) $7853
1910.305 B02 I
- Issued
- Dec 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose. (a) Injection mold 950-2 - On or about November 01, 2018 480 volt 3 phase outlet box was missing the cover plate. - Injection Molder 950-2 - Injection Molder110
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07
- Issued
- Dec 12, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): 29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner. (a) Hazmat Area - On or about November 01, 2018 energized 208 volt single phase temporary flexible conductor was not installed in a neat and workmanlike manner.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 I
- Issued
- Dec 12, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. (a) Hazmat Area - On or about November 01, 2018 energized 208 volt single phase temporary flexible conductor was not protected from abrasion.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G02 III
- Issued
- Dec 12, 2018
- Abate by
- Dec 28, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to the joints or terminal screws: (a) Injection Molding - On or about November 01, 2018 the outer sheathing was not connected to the strain relief connector. - No. 67 Thermulator - Injection Molder 2800
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Diversity-Vuteq LLC
View Diversity-Vuteq LLC's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in MS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343576294.