Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MS BUILDING SOLUTIONS INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MS BUILDING SOLUTIONS INC in 198A KENT ST., BROOKLYN, NY 11222 (NAICS 238130). OSHA activity number 343646006.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MS Building Solutions INC — free Get an email when a new federal OSHA severe-injury report for MS Building Solutions INC is published. One employer, no account, unsubscribe in one click.
Site address
198A KENT ST.
City
BROOKLYN
State
NY
ZIP
11222
Mailing
26-34 95TH ST, FLUSHING, NY 11369
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238130
Employees
3
Ownership type
A

3 citations on file for this inspection.

1926.404 F06

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 26, 2019
Penalty
Initial $2,842 · Current $2,842
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous.  a) 3rd floor:  Employees used an electric powered chop saw and an electric powered portable table saw to do carpentry and framing work. The saws were connected to a GFCI cord, which was routed to another extension cord that is routed to a nearby outlet device. The extension cord was missing a ground pin. On or about 12/07/18.
Recent events (1)
  • — Z (S) $2842

1926.405 A02 II A

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 26, 2019
Penalty
Initial $2,842 · Current $2,842
29 CFR 1926.405(a)(2)(ii)(A): Temporary wiring conductors did not run as multiconductor cord or cable assemblies or within raceways, and are subjected to physical damage.  a) 3rd floor:  Employees used an electric powered chop saw and an electric powered portable table saw to do carpentry and framing work. The saws were connected to a GFCI cord, which was connected to copper wires from an extension cord wrapped in electrical tape. The wires did not run as a cord or cable, and were exposed to physical damage. On or about 12/07/18.
Recent events (1)
  • — Z (S) $2842

1926.405 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 26, 2019
Abate by
Apr 3, 2019
Penalty
Initial $2,842 · Current $2,842
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers.  a) 3rd floor:  An energized electrical circuit breaker panel was not provided with a cover. Employees are exposed to the energized electrical parts of the panel during use. On or about 12/07/18.
Recent events (1)
  • — Z (S) $2842

View MS Building Solutions INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343646006.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.