Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: D&M RECYCLING, INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of D&M RECYCLING, INC in 313 ROBINSON STREET, GLEN WHITE, WV 25849 (NAICS 322299). OSHA activity number 343677084.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch D&M Recycling, INC — free Get an email when a new federal OSHA severe-injury report for D&M Recycling, INC is published. One employer, no account, unsubscribe in one click.
Establishment
D&M RECYCLING, INC
Site address
313 ROBINSON STREET
City
GLEN WHITE
State
WV
ZIP
25849
Mailing
PO BOX 1639, SOPHIA, WV 25921
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322299
Employees
10
Ownership type
A

18 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Dec 15, 2019
Penalty
Initial $3,978 · Current $2,980 Reduced

Hazardous substances E200

Section 5(a)(l) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm, including severe burns, to employees in that employees were exposed to fire and explosion hazards due to deficient design and/or implementation of preventive and/or protective measures in its dust collection system and related equipment, such as the following:         a) Shredding room - On or about 12/27/18,  a Baileigh enclosureless dust collector which handled combustible dust is located inside the building and immediately next to the work area, exposing employees to fire and deflagration hazards       Abatement Note: Among other methods, one feasible and acceptable abatement method to correct the hazard is to ensure that enclosureless dust collectors which are used indoors comply with NFPA 654 (2013) Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids.       In accordance with NFPA 654, Chapter 7, Section 7.13.1.1.2 (4) the criteria that needs to be met in order to allow a dust collector indoors are:     (a) The filter medium is not shaken or pressure-pulsed to dislodge dust during operation.   (b) The AMS is not used to vent or serve metal grinders, hot work processes, or machinery that can produce sparks.   (c) The AMS is not used to vent or serve sanders, abrasive planers, or similar sanding process equipment.   (d)*Each collector system has a maximum air flowhandling capacity of 3000 cfm (1.4 m3/sec).   (e) The fan motor is suitable for Class II, Division 2, or Class III, as appropriate.   (f) The collected dust is removed daily or more frequently if necessary to ensure efficient operation and to limit the collected dust to less than 22 lb (10 kg).   (g) The collector is located at least 20 ft (6.1 m) from any means of egress or area routinely occupied by personnel.   (h)*Multiple collectors in the same room are separated from each other by at least 20 ft (6.1 m).   (i)*The minimum ignition energy (MIE) of the collected materials is greater than 500 mJ.   (j) The fan construction is spark resistant and meets the criteria in 7.12.2.5.   (k) The filter medium is not located within 35 ft (10.7 m) of any open flame or hot surface capable of igniting a dust cloud of the material it contains.  **NOTE** all the criteria must meet
Recent events (2)
  • — I (S) $2980
  • — Z (S) $3978

1910.22 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 24, 2019
Penalty
Initial $0 · Current $0

Hazardous substances E200

29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition:    a) Shredding room - On or about 12/20/18, the employer did not keep vertical and elevated horizontal surfaces of the work area free from hazardous accumulations of combustible dust, exposing employees to fire and explosion hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 24, 2019
Penalty
Initial $0 · Current $0

Hazardous substances E200

29 CFR 1910.22(a)(2): The floor of each workroom was not maintained in a clean condition.     a) Shredding room - On or about 12/20/18, the employer did not keep the floor of the work area free from hazardous accumulations of combustible dust, exposing employees to fire and explosion hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 G04

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Jun 27, 2019
Penalty
Initial $2,273 · Current $1,700 Reduced
29 CFR 1910.36(g)(4): Objects projecting into the exit route reduced the width of the exit route to less than the minimum width requirements for exit routes:       a) Document Warehouse - On or about 12/20/18, the employer stored materials in exit routes which reduced their width to less than 28 inches, exposing employees to fire hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $2273

1910.37 A03

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Jun 27, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    a) Truck unloading area - On or about 12/20/18, the employer stored materials in exit routes, obstructing access to the exits,  exposing employees to fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B02

Serious Gravity 5 3 instances 10 exposed
Issued
Jun 19, 2019
Abate by
Jun 27, 2019
Penalty
Initial $2,273 · Current $1,700 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":    a) Warehouse - On or about 12/20/18, the employer did not mark exit doors, exposing employees to fire hazards.    b) Loading dock - On or about 12/20/18, the employer did not mark exit doors, exposing employees to fire hazards.    c) Shredding room - On or about 12/20/18, the employer did not mark exit doors, exposing employees to fire hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $2273

1910.212 A03 II

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 19, 2019
Abate by
Jun 27, 2019
Penalty
Initial $2,842 · Current $2,130 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):      a) Shredding room - On or about 12/20/18, the guard for the paper shredder was damaged, exposing employees to amputation hazards.
Recent events (2)
  • — I (S) $2130
  • — Z (S) $2842

1910.303 B07

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Jul 1, 2019
Penalty
Initial $2,273 · Current $1,700 Reduced
29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner:    a) Restroom - On or about 12/20/18, a the ceiling light had connections made outside junction box, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $2273

1910.305 G02 III

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Jul 1, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a) Restroom - On or about 12/20/18, the flexible cord from a ceiling light had connections which were not provided with strain relief, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jun 27, 2019
Penalty
Initial $3,410 · Current $2,550 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.    a) Shredding room - On or about 12/20/18, a junction box containing energized conductors was missing a cover, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2550
  • — Z (S) $3410

1910.303 B07 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 23, 2019
Penalty
Initial $2,842 · Current $2,130 Reduced
29 CFR 1910.303(b)(7)(iv): Electric equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.      a) Shredding room - On or about 12/20/18, a duplex receptacle was damaged and exposing energized parts, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2130
  • — Z (S) $2842

1910.305 D02

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 19, 2019
Abate by
Jul 23, 2019
Penalty
Initial $2,842 · Current $2,130 Reduced
29 CFR 1910.305(d)(2): Panelboards mounted in cabinets, cutout boxes, or enclosures designed for the purpose and were not dead front.     a) Restroom - On or about 12/20/18, a 240V circuit panel was not covered with a dead front, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2130
  • — Z (S) $2842

1910.147 C01

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Aug 1, 2019
Penalty
Initial $3,978 · Current $2,980 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:      a) Shredding room - On or about 12/27/18, the employer did not develop energy control procedures for employees performing servicing and maintenance on an Allegheny 1000 series industrial paper shredder, exposing employees to amputation hazards.
Recent events (2)
  • — I (S) $2980
  • — Z (S) $3978

1910.134 C01

Other-than-serious 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 23, 2019
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(c)(1): A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:      a) Shredding room - On or about 12/27/18, the employer did not develop a written respiratory protection program when it required employees to use respirators to control exposure to dust, exposing employees to respiratory hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 G01 I A

Other-than-serious 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Aug 1, 2019
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(g)(1)(i)(A): Respirators with tight-fitting facepieces were worn by employees who had facial hair that came between the sealing surface of the facepiece and the face or that interfered with valve function:      a) Shredding room - On or about 12/27/18, an employee required to use a respirator by the employer was allowed to use the respirator with facial hair which interfered with the seal of the respirator, exposing employees to respiratory hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.134 K

Other-than-serious 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Aug 1, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.134(k): The employer did not provide comprehensive, understandable training which did not occur annually and/or more often if necessary:      a) Shredding room - On or about 12/27/18, the employer did not provide training to employees required to use respirators by the employer, exposing employees to respiratory hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 23, 2019
Penalty
Initial $0 · Current $0
9 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:      a) Shredding Room - On or about 12/27/18, an extension cord was used in lieu of fixed wiring to provide power to a garage door opener, exposing employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV D

Other-than-serious 1 instance 2 exposed
Issued
Jun 19, 2019
Abate by
Jul 23, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces:    a) Shredding Room - On or about 12/27/18, an extension cord was used to provide power to a garage door opener was attached to building surfaces, exposing employees to electrical hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View D&M Recycling, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343677084.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.