SCHERTZ, TX —
OSHA Inspection: MANCO STRUCTURES, LTD
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of MANCO STRUCTURES, LTD in 6106 FM 3009, SCHERTZ, TX 78154 (NAICS 327390). OSHA activity number 343691010.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MANCO STRUCTURES, LTD
- Site address
- 6106 FM 3009
- City
- SCHERTZ
- State
- TX
- ZIP
- 78154
- Mailing
- 6106 FM 3009, SCHERTZ, TX 78154
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327390
- Employees
- 50
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.132 A
- Issued
- Feb 6, 2019
- Penalty
- Initial $5,636 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: On or about January 2, 2019 and times prior thereto, an employee was observed operating the CAT 950F front loader without the use of his seatbelt. This condition exposed employees to ejection and crushed-by hazards in the event of a tip over.
Recent events (2)
- — I (S) $0
- — Z (S) $5636
1910.303 E01 II
- Issued
- Feb 6, 2019
- Abate by
- Feb 19, 2019
- Penalty
- Initial $3,381 · Current $3,381
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary: On or about January 8, 2018 and times prior thereto, panel boxes were observed without voltage markings in the following instances; exposing employees to the hazard of electrical shock. Instance A: In the Batch Plant 2, the panel boxes located behind the operators chair Instance B: Outside the Quality Control building, near the entrance door.
Recent events (2)
- — I (O) $3381
- — Z (S) $3381
1910.303 F02
- Issued
- Feb 6, 2019
- Abate by
- Feb 19, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about January 8, 2018 and times prior thereto, the circuit breakers in the panel box located outside the quality control room were not legibly marked to show their purpose. This condition exposed employees to unexpected energization and other electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Feb 6, 2019
- Abate by
- Mar 5, 2019
- Penalty
- Initial $3,381 · Current $2,025 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about January 8, 2019 and times prior thereto, an outlet box in Batch Plant area was observed without an electrical faceplate. This condition exposed the Batch Plant operator and other employees to electrical hazards.
Recent events (2)
- — I (O) $2025
- — Z (S) $3381
1910.305 G01 III
- Issued
- Feb 6, 2019
- Abate by
- Mar 5, 2019
- Penalty
- Initial $3,381 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iii): Flexible cords and cables were used for purposes prohibited by subparagraphs (A) through (E) of this paragraph: On or about January 8, 2019 and times prior thereto, a flexible cord with a power strip was used in place of permanent wiring in the Batch Plant control panel house. This condition exposed employees to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $3381
1910.305 G02 III
- Issued
- Feb 6, 2019
- Abate by
- Feb 19, 2019
- Penalty
- Initial $0 · Current $1,600
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: On or about January 8, 2019, the outer layer of insulation on the attachment plug for the electric scale in the Batch Plant was partially frayed.
Recent events (2)
- — I (O) $1600
- — Z (S) $0
More inspections at Manco Structures, LTD
View Manco Structures, LTD's full OSHA safety record →
More inspections in this industry (NAICS 327390)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343691010.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.