On , OSHA opened a planned safety inspection of POWER ELECTRIC COMPANY in NORFOLK NAVAL SHIPYARD BUILDING M-32, PORTSMOUTH, VA 23709 (NAICS 238210). OSHA activity number 343707147.

Watch Power Electric Company — free Get an email when a new federal OSHA severe-injury report for Power Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
NORFOLK NAVAL SHIPYARD BUILDING M-32
City
PORTSMOUTH
State
VA
ZIP
23709
Mailing
1954 DIAMOND HILL ROAD, CHESAPEAKE, VA 23324
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
60
Ownership type
A

2 citations on file for this inspection.

1926.404 F06

Other-than-serious 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $1392.00 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:  a)   Building M-32: On or about 01/10/2019, the path to ground for an aluminum recessed light was not continuous and permanent in that the ground wire was not connected at the sliced joint.   b)   Building M-32: On or about 01/10/2019, the path to ground for the Metal clad cable used with temporary lights was not continuous and permanent in that the Metal Clad cable was not connected to an enclosure that was grounded.   Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $1392
  • — Z (S) $3978

1926.405 B01

Other-than-serious 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $3978.00 · Current $1392.00 Reduced
29 CFR 1926.405(b)(1): Openings in boxes, cabinets, and fittings through which conductors entered were not effectively closed:  a)     Building M-32, 3rd floor, 120 volts breaker panel: On or about 01/10/2019, the bottom section of the enclosure had (4) four openings that were not provided with covers as a result exposed employees to a possible arc flash fire.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.