Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: ACE CASE MANUFACTURING, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ACE CASE MANUFACTURING, LLC in 490 LONG SPRINGS RD., STEELVILLE, MO 65565 (NAICS 339920). OSHA activity number 343728838.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ACE Case Manufacturing, LLC for free Get an email when a new federal OSHA severe-injury report for ACE Case Manufacturing, LLC is published. One employer, no account, unsubscribe in one click.
Site address
490 LONG SPRINGS RD.
City
STEELVILLE
State
MO
ZIP
65565
Mailing
160 N. MAIN ST., SAINT CLAIR, MO 63077
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339920
Employees
18
Ownership type
Private (A)

6 citations on file for this inspection.

1910.106 E06 I

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $3,220 · Current $2,254 Reduced
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors from sources such as open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat:  Containers of flammable liquids, in the glue room, were not grounded and bonded when transfer of contents was made.
Recent events (2)
  • · I (S) $2254
  • · Z (S) $3220

1910.106 E06 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected.  Containers of flammable liquids, in the glue room, were not grounded and bonded when transfer of contents was made.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.107 C06

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:  Spraying of flammable liquids was conducted in work space without spray booths or explosion proof equipment to prevent potential ignition of the flammable liquids being sprayed because of static electricity from non-explosion proof electrical outlets, electrical switches, and exhaust fan.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.107 C07

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.107(c)(7): Electric lamps outside of but within 20 feet of spraying area(s), and not separated therefrom by partition(s), were not protected from mechanical injury by suitable guards or by location:  Spraying of flammable adhesive was conducted in work space without explosion proof equipment to prevent potential ignition of the flammable liquids being sprayed because of static electricity from non-explosion proof lighting.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $1,932 · Current $1,352 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  The glue room exhaust fan was operated without a ground pin.
Recent events (2)
  • · I (S) $1352.4
  • · Z (S) $1932

1910.334 A02 II

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 12, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:  An extension cord and cutter power cord were used with the insulation damaged; inner conductors were exposed.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343728838.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.