TORRINGTON, CT —
OSHA Inspection: ATRIA SENIOR LIVING, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ATRIA SENIOR LIVING, INC. in 376 GOSHEN ROAD, TORRINGTON, CT 06790 (NAICS 623312). OSHA activity number 343732715.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATRIA SENIOR LIVING, INC.
- Site address
- 376 GOSHEN ROAD
- City
- TORRINGTON
- State
- CT
- ZIP
- 06790
- Mailing
- 376 GOSHEN ROAD, TORRINGTON, CT 06790
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623312
- Employees
- 65
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 3, 2019
- Penalty
- Initial $4,517 · Current $2,259 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Kitchen: On, or about, January 22, 2019, two box fans designed for use in a residential location were used for air circulation in the dishroom and main kitchen area.
Recent events (3)
- — F (O) $2258.5
- — C (S) $4517
- — Z (S) $4517
1910.303 G01 II
- Issued
- Apr 3, 2019
- Penalty
- Initial $4,517 · Current $2,259 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: A. Boiler Room: On, or about, January 22, 2019, boxes of ceiling tiles and a fan housing were stored in front of a bank of electrical disconnect switches. B. Boiler Room: On, or about, January 22, 2019, a wet/dry vacuum, hand cart and part of a refrigerator/dehumidifier were stored in front of the disconnect switches for the cooling towers.
Recent events (3)
- — F (O) $2258.5
- — C (S) $4517
- — Z (S) $4517
1910.304 F01 IV
- Issued
- Apr 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: Basement Service Corridor, Workshop: On, or about, January 22, 2019, a door and bathroom vanity cabinet were stored against the access door the elevator equipment room, limiting access to the fused electrical disconnect switch for the elevator.
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.304 B04
- Issued
- Apr 3, 2019
- Penalty
- Initial $4,517 · Current $2,259 Reduced
General-duty citation text
29 CFR 1910.304(b)(4): Outlet devices had an ampere rating less than the load being served: Maintenance Office: On, or about, a coffee maker, microwave oven and two refrigerators were energized through a 20 ampere wall outlet. The combined load (in amperes) of the appliances was greater than the rating of the outlet.
Recent events (3)
- — F (O) $2258.5
- — C (S) $4517
- — Z (S) $4517
1910.305 B02 I
- Issued
- Apr 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: A. Maintenance Office: On, or about, January 22, 2019, a cover had not been provided on the wall mounted outlet used to energize a coffee pot, microwave oven and two refrigerators. B. Kitchen: On, or about, January 22, 2019, a cover had not been provided on a wall mounted outlet located between a door and a refrigerator.
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.1030 C01 II B
- Issued
- Apr 3, 2019
- Abate by
- May 20, 2019
- Penalty
- Initial $7,084 · Current $4,723 Reduced
General-duty citation text
29 CFR 1910.1030(c)(1)(ii)(B): The employer's Exposure Control Plan did not include the schedule and method of implementation for 29 CFR 1910.1030(d), Methods of Compliance and 29 CFR 1910.1030(f), Hepatitis B Vaccination and Post-Exposure Evaluation and Follow-up: Facility: On, or about, January 30, 2019, the Exposure Control Plan contained the following deficiencies: A. The Exposure Control Plan did not include procedures to follow to address blood spills. B. The Exposure Control Plan did not address post vaccination antibody testing and what procedures would be followed in the instance of a non-responder to the series. Also, the acceptance form for the Hepatitis B vaccination series included a waiver of liability, which does not comply with the at no cost provision of the regulation.
Recent events (3)
- — F (S) $4722.5
- — C (S) $7084
- — Z (S) $7084
1910.1030 C01 V
- Issued
- Apr 3, 2019
- Abate by
- May 20, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(c)(1)(v): The employer, who is required to establish an Exposure Control Plan, did not solicit input from non-managerial employees responsible for direct patient care who are potentially exposed to injuries from contaminated sharps in the identification, evaluation and selection of effective engineering and work practice controls and did not document the solicitation in the Exposure Control plan: Facility: On, or about, January 30, 2019, the employer had not solicited input from nursing staff regarding safer needle devices that were used in the facility.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.1030 D04 II A
- Issued
- Apr 3, 2019
- Abate by
- May 20, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(d)(4)(ii)(A): Contaminated work surfaces were not decontaminated immediately or as soon as feasible when surfaces were overtly contaminated or after any spill of blood or other potentially infectious materials: Facility: On, or about, January 30, 2019, blood spills in the facility had not been cleaned using an appropriate disinfectant in that: A. Blood was cleaned from a carpeted area using Whittaker Crystal Dry Extra. The facility did not supply a disinfectant that was approved for use on a carpeted surface. B. Blood was cleaned using Ecolab 73 Disinfecting Acid Bathroom Cleaner using a contact time of fifteen seconds in accordance with the facilities housekeeping general cleaning procedures. The facility lacked a procedure and training to instruct staff that the disinfectant required a contact time of five minutes to be effective against blood borne pathogens in accordance with the manufacturers instructions.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.36 G02
- Issued
- Apr 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. Boiler Room: On, or about, January 22, 2019, items such as a pallet and vent cover were stored in the exit access path leading to the exterior exit door.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.132 A
- Issued
- Apr 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(a): Protective equipment was not maintained in a sanitary and reliable condition: Kitchen: On, or about, January 22, 2019, a pair of chemical splash goggles that was provided for use when using Ecolab Greasestrip Plus, a corrosive liquid, was dirty and had a broken strap.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
1910.1200 G08
- Issued
- Apr 3, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s): Kitchen: On, or about, January 22, 2019, the company did not have a Safety Data Sheet available for Ecolab Grease Express High Temp Grill Cleaner, a new product that had recently been obtained and was available for use.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Atria Senior Living, INC.
View Atria Senior Living, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 623312)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343732715.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.