NORTH GROSVENORDALE, CT —
OSHA Inspection: SUPERIOR BAKERY, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SUPERIOR BAKERY, INC. in 72 MAIN STREET, NORTH GROSVENORDALE, CT 06255 (NAICS 311811). OSHA activity number 343734489.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUPERIOR BAKERY, INC.
- Site address
- 72 MAIN STREET
- City
- NORTH GROSVENORDALE
- State
- CT
- ZIP
- 06255
- Mailing
- 72 MAIN STREET, NORTH GROSVENORDALE, CT 06255
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311811
- Employees
- 63
- Ownership type
- A
Citations
31 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 23, 2019
- Penalty
- Initial $6,630 · Current $4,641 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck-by hazards: Mixer Area: On, or about, January 24, 2019, the spreader bar/chains provided for the stainless steel dough tub were not provided with a lifting capacity marking or tag and were not subject to documented inspections.
Recent events (2)
- — I (S) $4641
- — Z (S) $6630
1910.184 E02 II
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.184(e)(2)(ii): Makeshift link(s) or fastener(s) formed from bolts, or other such attachment(s) were used to connect links or fastenings on alloy steel chain sling(s): Mixer Area: On, or about, January 24, 2019, stainless steel bolts were used to secure the shackle connector on the dough tub spreader bars. The bolts did not have the same strength as the alloy chain and were not designed as shackle bolts/pins.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.23 E03 II
- Issued
- Apr 23, 2019
- Penalty
- Initial $6,630 · Current $4,641 Reduced
General-duty citation text
29 CFR 1910.23(e)(3)(ii): Mobile ladder stand platforms with a platform height of 4 to 10 feet (1.2 m to 3 m) did nothave, in the platform area, handrails with a vertical height of at least 36 inches (91 cm) and midrails: Dough Area: On, or about, January 31, 2019, the rolling platform that was used to clean the hopper on the dough machine was not provided with adequate railings or chains. The chains that had been provided were removed to provide easier access to the hopper.
Recent events (2)
- — I (S) $4641
- — Z (S) $6630
1910.28 B01 I
- Issued
- Apr 23, 2019
- Abate by
- Jan 31, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet (1.2 m) or more above a lower level was protected from falling by one or more of the following: Guardrail systems, safety net systems, or personal fall arrest systems: A. Bread Proofer: On, or about, January 24, 2019, employee who accessed the top of the enclosure to perform maintenance activities were not provided with a fall protection system such as a guardrail system or personal fall arrest/restraint equipment. B. Fermentation Cooler: On, or about, January 31, 2019, an employee was observed on the top of the cooler performing sanitation activities. The employee was not provided with safe access nor was he provided with an adequate fall protection system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.29 B01
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.29(b)(1): The top edge height of top rails, or equivalent guardrail system members, were not 42 inches, plus or minus 3 inches, above the walking-working surface: Front Stairway near Breakroom: On, or about, January 24, 2019, the railing provided along the stairway was measured to be 32 inches high.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.36 A03
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $6,630 · Current $4,641 Reduced
General-duty citation text
29 CFR 1910.36(a)(3): An opening into an exit was not protected by a self-closing fire door that remains closed or automatically closes in an emergency upon the sounding of a fire alarm or employee alarm system. Each fire door, including its frame and hardware, must be listed or approved by a nationally recognized testing laboratory: Front Breakroom Stairway: On, or about, January 31, 2019, the exit stairway that provided egress from both the main level and the lower level was not enclosed at the top landing or at the landing that led to the lower level. In the event of an emergency, the stairway could be compromised by the lack of protection from smoke and fire. Abatement Note: The wall opening that provides a window between the Breakroom and the hall may need to be closed in to limit the number of openings into the exit enclosure.
Recent events (2)
- — I (S) $4641
- — Z (S) $6630
1910.36 B01
- Issued
- Apr 23, 2019
- Abate by
- Nov 30, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(b)(1): At least two exits routes were not available to permit prompt evacuation of employees during an emergency: Finished Goods Warehouse: On, or about, January 31, 2019, the warehouse was not provided with a sufficient number of exits. Per NFPA 101 Life Safety Code, the maximum length of a dead-end or common path of travel was limited to 50 feet. The travel distance in the warehouse to the freezer area exceeded 50 feet.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.36 D01
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: Freezer: On, or about, January 24, 2019, the freezer was provided with an unmarked knob to allow an occupant to release the door from the chain drive mechanism. The knob was not marked to indicate its function and special knowledge was needed for an employee to know how to use it.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B01
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route: Freezer: On, or about, January 24, 2019, emergency lighting was not provided in the freezer.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B04
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: Oven Area: On, or about, April 5, 2019, the route to the nearest exit doors was not visibly obvious and directional signs had not been provided.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.132 D01
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $5,304 · Current $3,713 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): Wash Area: On, or about, January 24, 2019, the company had not conducted a Hazard Assessment to determine what personal protective equipment needed to be worn by employees who used sanitation chemicals such as, but not limited to, ChemStation 3131, a corrosive liquid.
Recent events (2)
- — I (S) $3712.8
- — Z (S) $5304
1910.133 A01
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.133(a)(1): Protective eye and face equipment was not required where there was a reasonable probability of injury that could be prevented by such equipment: Wash Area: On, or about, January 24, 2019, employees who used ChemStation 3131, a corrosive liquid, were not provided with adequate eye and face protection.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.263 G03
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $5,304 · Current $3,713 Reduced
General-duty citation text
29 CFR 1910.263(g)(3): Stopping device(s) were not within easy reach of the operator(s) feeding the moulder(s): Bread Sheeter: On, or about, January 24, 2019, an emergency stop device was not provided at the start end of the bread sheeter (moulder). The operator worked in close proximity to several conveyor terminations.
Recent events (2)
- — I (S) $3712.8
- — Z (S) $5304
1910.303 B02
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $5,304 · Current $3,713 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: In the following locations, relocatable power taps were energized through an extension cord, which is not an acceptable practice in the UL Whitebook for the use of power tap devices: A. Bread Oven, Start End: On, or about, January 24, 2019, a relocatable power tap was energized through a yellow extension cord to power a pedestal fan and an oven camera monitor. B. Roll Oven, Finish End: A relocatable power tap was energized through a yellow and black extension cord to power a water cooler and oven camera monitor.
Recent events (2)
- — I (S) $3712.8
- — Z (S) $5304
1910.305 G01 IV A
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: A. Bread Oven, Start End: On, or about, January 24, 2019, a yellow extension cord was used to energize a pedestal fan and oven camera monitor. B. Roll Oven, Finish End: On, or about, January 24, 2019, a yellow and black extension cord was used to energize a pedestal fan and oven camera monitor. C. Roll Packaging, Start End: On, or about, January 31, 2019, a red extension cord was used to energize a wall mounted fan. D. Maintenance Shop: On, or about, January 31, 2019, a yellow extension cord was used to energize an overhead light fixture.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Apr 23, 2019
- Abate by
- Aug 10, 2019
- Penalty
- Initial $3,978 · Current $2,785 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: A. Wash Area: On, or about, January 24, 2019, approximately thirteen circuit breakers that were located in an Eaton wall mounted panelboard were not labeled to indicate their purpose. The circuit breakers were in the on position. B. Receiving Dock: On, or about, January 24, 2019, approximately three circuit breakers that were located in Panel P2 were not labeled to indicate their purpose. C. Receiving Dock: On, or about, January 24, 2019, approximately 20 circuit breakers that were located in Panel P2A were not labeled to indicate their purpose.
Recent events (2)
- — I (S) $2784.6
- — Z (S) $3978
1910.303 G01 I A
- Issued
- Apr 23, 2019
- Abate by
- Jun 10, 2019
- Penalty
- Initial $5,304 · Current $3,713 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Roll Conveyor, Finish End: Metal railings that were installed in front of the Depanner and Conveyor control enclosures limited the working space in front of the equipment to less than the required distance required by Table S-1 which was 42 inches.
Recent events (2)
- — I (S) $3712.8
- — Z (S) $5304
1910.303 G01 II
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Dry Goods Warehouse: On, or about, January 24, 2019, a storage rack was located in front of Subpanel SB-12, a Cutler-Hammer panelboard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 F01 IV
- Issued
- Apr 23, 2019
- Abate by
- Jan 31, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: A. Roll Oven, Finish End: On, or about, January 24, 2019, the overcurrent devices contained in three panelboards mounted on the wall above the oven discharge conveyor were not readily accessible due to their height. A ladder was required to reach the circuit breakers located in the middle and top sections of each panel. B. Maintenance Shop: On, or about, January 31, 2019, a refrigerator and storage drawers were blocking access to the Cutler-Hammer wall mounted panelboard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 B04
- Issued
- Apr 23, 2019
- Penalty
- Initial $3,381 · Current $2,367 Reduced
General-duty citation text
29 CFR 1910.304(b)(4): Outlet devices had an ampere rating less than the load being served: A. Breakroom: On, or about, January 24, 2019, two microwave ovens were energized through the same 15 ampere wall receptacle. The combined load of the two microwave ovens was 25.8 amperes. B. Maintenance Shop: On, or about, January 31, 2019, a microwave oven, toaster oven and coffee maker were energized through the same 20 ampere wall receptacle. The combined load of any two of the appliances exceeded the rating of the receptacle.
Recent events (2)
- — I (S) $2366.7
- — Z (S) $3381
1910.304 B04 II B
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord-and plug-connected load in excess of the maximum specified in Table S-4: Maintenance Shop: On, or about, January 31, 2019, a 15 ampere relocatable power tap was used to energize a microwave oven, toaster oven and coffee maker. The maximum load permitted on the power tap was 12 amperes. The rating for each of the three appliances exceeded the 12 ampere limit.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Apr 23, 2019
- Penalty
- Initial $6,630 · Current $4,641 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: A. Slicing Area: On, or about, January 31, 2019, the ground pin was missing from the plug on the Avery Weigh Tronix ZQ375 scale. B. Maintenance Shop: On, or about, April 5, 2019, the ground pin was missing from the plug on the relocatable power tap that was used to energize a microwave oven, refrigerator and overhead light fixture.
Recent events (2)
- — I (S) $4641
- — Z (S) $6630
1910.305 B01 II
- Issued
- Apr 23, 2019
- Penalty
- Initial $4,508 · Current $3,156 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: A. Receiving Dock: On, or about, January 24, 2019, an opening was left in the dead front panel of Panel P2, a Siemens panelboard. B. Bread Oven, Start End: On, or about, January 24, 2019, a knockout was left open on the top of a duplex receptable box mounted on the right side of the oven enclosure. C. Roll Oven, Finish End: On, or about, January 24, 2019, an opening in the dead front of Panel RU2, a General Electric panelboard, was covered with duct tape. D. Maintenance Shop: On, or about, April 5, 2019, two openings were left in the dead front of the Cutler-Hammer panelboard.
Recent events (2)
- — I (S) $3155.6
- — Z (S) $4508
1910.305 B02 I
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Breakroom: On or about, January 24, 2019, a cover had not been provided on a wall mounted junction box near the microwave cart.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1904.41 A02
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.41(a)(2) Annual electronic submission of OSHA Form 300A Summary of Work-Related Injuries and Illnesses by establishments with 20 or more employees but fewer than 250 employees in designated industries. If your establishment had 20 or more employees but fewer than 250 employees at any time during the previous calendar year, and your establishment is classified in an industry listed in appendix A to subpart E of this part, then you must electronically submit information from OSHA Form 300A Summary of Work-Related Injuries and Illnesses to OSHA or OSHA's designee. You must submit the information once a year, no later than the date listed in paragraph (c) of this section of the year after the calendar year covered by the form. Located at the Superior Bakery, Inc. 70 Main Street, North Grosvenordale, Connecticut: On or about April 9, 2019, the employer failed during calendar year 2018, to electronically submit information from their OSHA Form 300A or equivalent by March 2, 2019. a). The establishment employed 63 employees and is classified under NAICS Code 311811 during calendar year 2018.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.25 B01
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.25(b)(1): The employer did not ensure handrails, stair rail systems, and guardrail systems were provided in accordance with 1910.28: Maintenance Shop: On, or about, January 31, 2019, a midrail was not provided on the set of stairs that led from the Maintenance Shop to the main production floor.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.36 G02
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. Roll Packaging: On, or about, January 31, 2019, the exit passage that ran between the conveyor system and interior block wall was reduced to 19 inches wide where the hose reel and reject table were located.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.146 C02
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(2): The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces: Silo Area: On, or about, January 31, 2019, two storage silos were not marked to indicate that they were permit required confined spaces.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.219 E01 I
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs seven -7 feet or less from the floor level were not enclosed with a guard or provided with a guard that extended to at least fifteen inches above the belt: Maintenance Shop: On, or about, January 31, 2019, guards were not provided on the change speed belt openings on Bridgeport milling machine serial number J41209.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.263 I01
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.263(i)(1): Proof boxes. All door locks were not operable both from within and outside the box: Roll Proofer: On, or about, January 24, 2019, the interior release latch for two of the proofer access doors was broken and could no longer be operated from the inside of the enclosure.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F06 II
- Issued
- Apr 23, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals: Fuel Tank Area: On, or about, January 31, 2019, a 10,000 gallon storage tank that contained #2 Fuel Oil, a Category 3 flammable liquid, was not provided with a label or placard to indicate the contents and the hazards associated with the contents.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Superior Bakery, INC.
View Superior Bakery, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311811)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343734489.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.